APC by Schneider Electric SMX2200RMLV2U vs CyberPower PR2200RT2UC

UPS COMPARISON

APC by Schneider Electric SMX2200RMLV2U vs CyberPower PR2200RT2UC: Specification Comparison

Both the APC SMX2200RMLV2U and CyberPower PR2200RT2UC are 2U rack/tower-convertible line-interactive UPS units rated at 2200 VA, designed for small-to-mid datacenter, server room, and network closet applications. This comparison examines how each handles power protection, runtime and battery characteristics, and connectivity—the three axes that most directly affect purchasing decisions for this class of UPS. Neither unit is evaluated on price or brand preference; all claims derive strictly from the specifications provided.



How does each UPS handle input tolerance, surge protection, and output quality?

The SMX2200RMLV2U accepts an input voltage range of 70–153 V on a NEMA L5-30P twist-lock plug and produces 120 V AC output at 1980 W (power factor 0.9). Its surge energy rating is 540 Joules, and transfer time is 4 ms. Output waveform type is not explicitly stated in the provided specs.

The PR2200RT2UC accepts 75–149 V input and delivers 120 V AC output at a full 2200 W with a unity power factor (1.0). Its surge energy rating is substantially higher at 2430 Joules, and transfer time is 6 ms. The spec sheet explicitly confirms a true sine wave output and EMI/RFI noise filtering. Noise level is rated at 52.5 dB.

On surge protection, the PR2200RT2UC's 2430 J rating is 4.5× the SMX2200RMLV2U's 540 J. The APC unit has the faster transfer time (4 ms vs. 6 ms) and a wider low-end voltage tolerance (70 V vs. 75 V). The CyberPower unit's unity power factor means it can deliver its full 2200 W rating to connected loads; the APC unit is derated to 1980 W.


What runtime and battery characteristics does each unit offer at full and half load?

The SMX2200RMLV2U provides a specified backup runtime of 10 minutes at full load and 25 minutes at half load. Battery chemistry is sealed lead acid (maintenance-free, sealed, spill-proof). Recharge time is 3 hours. Compatible replacement battery cartridges are identified as APCRBC117 and APCRBC117J. The unit includes a Smart-Slot expansion interface, which supports optional APC network management cards and extended battery module accessories.

The PR2200RT2UC spec sheet does not provide runtime figures at full or half load in the data supplied. Battery type, recharge time, and replacement battery part numbers are also absent from the provided specifications. No expansion slot or extended runtime accessory compatibility is noted in the provided specs.

For buyers where runtime visibility is a procurement requirement, the SMX2200RMLV2U offers documented runtime figures (10 min full / 25 min half load) and a named Smart-Slot for expansion cards. The PR2200RT2UC's runtime under load cannot be confirmed from the specifications provided.


How do the outlet configurations, management interfaces, and certifications compare?

The SMX2200RMLV2U provides 8 output receptacles: 6× NEMA 5-15R and 2× NEMA 5-20R. It includes 1 Smart-Slot expansion bay (supports APC network management and environmental monitoring accessories). Certifications listed include UL 1778, UL 1449, FCC Part 15 Class A, TUV, CSA, EN 55022 Class A, BSMI, NOM, VCCI Class A, EN 50091-2, and REACH.

The PR2200RT2UC provides 8× NEMA 5-20R receptacles and includes cloud management capability (noted in the product title as 'Cloud'). Maximum output current is rated at 15 A. Audible alarms are confirmed. Specific certifications and management card slot availability are not detailed in the provided specifications.

The APC unit mixes 5-15R and 5-20R outlets, which accommodates a broader variety of attached device power cords without adapters. The CyberPower unit standardizes on 8× NEMA 5-20R, providing higher-amperage receptacles throughout. Cloud management is referenced for the PR2200RT2UC but the underlying platform is not specified in the provided data. The SMX2200RMLV2U has an extensive published certification list; comparable certifications for the PR2200RT2UC are not available in the provided specs.


Which should you choose: the SMX2200RMLV2U or the PR2200RT2UC?

Our take: The SMX2200RMLV2U is the stronger choice when documented runtime, expansion flexibility, and broad outlet variety are primary requirements. It provides verified backup times (10 min full load / 25 min half load), a Smart-Slot for network management cards, and a mix of 5-15R and 5-20R outlets suiting diverse equipment. The PR2200RT2UC counters with a 2430 J surge energy rating—4.5× the APC's 540 J—and a unity power factor that allows the full 2200 W output rating, versus the APC's 1980 W. The CyberPower also explicitly confirms true sine wave output and cloud management capability, though runtime figures and certification details are absent from the specs provided. Buyers prioritizing maximum surge protection and full watt-rated output for devices sensitive to waveform quality should evaluate the PR2200RT2UC further. Buyers who need verified runtime data, named replacement batteries, or expansion card compatibility will find the SMX2200RMLV2U better documented for those requirements.


Side-by-Side Comparison

Spec-for-spec, from manufacturer data.

SpecificationAPC by Schneider Electric SMX2200RMLV2UCyberPower PR2200RT2UC
UPS TopologyLine-InteractiveLine-Interactive
VA Rating2200 VA2200 VA
Watt Rating1980 W2200 W
Power Factor0.9 (derived)1.0
Output WaveformNot specified in provided specsSine wave
Input Voltage Range70–153 V75–149 V
Input ConnectionNEMA L5-30PNot specified in provided specs
Output Voltage120 V AC120 V AC
Transfer Time4 ms6 ms
Surge Energy Rating540 J2430 J
Output Receptacles6x NEMA 5-15R + 2x NEMA 5-20R (8 total)8x NEMA 5-20R
Runtime at Full Load10 minNot specified in provided specs
Runtime at Half Load25 minNot specified in provided specs
Battery Recharge Time3 hoursNot specified in provided specs
Expansion Slot1x Smart-SlotNot specified in provided specs
Form Factor2U Rack/Tower convertible2U Rack/Tower convertible

Frequently Asked Questions

Which should you choose: the SMX2200RMLV2U or the PR2200RT2UC?

The SMX2200RMLV2U is the stronger choice when documented runtime, expansion flexibility, and broad outlet variety are primary requirements. It provides verified backup times (10 min full load / 25 min half load), a Smart-Slot for network management cards, and a mix of 5-15R and 5-20R outlets suiting diverse equipment. The PR2200RT2UC counters with a 2430 J surge energy rating—4.5× the APC's 540 J—and a unity power factor that allows the full 2200 W output rating, versus the APC's 1980 W. The CyberPower also explicitly confirms true sine wave output and cloud management capability, though runtime figures and certification details are absent from the specs provided. Buyers prioritizing maximum surge protection and full watt-rated output for devices sensitive to waveform quality should evaluate the PR2200RT2UC further. Buyers who need verified runtime data, named replacement batteries, or expansion card compatibility will find the SMX2200RMLV2U better documented for those requirements.

Which UPS offers better surge protection, the SMX2200RMLV2U or the PR2200RT2UC?

Based on the provided specifications, the PR2200RT2UC has a substantially higher surge energy rating at 2430 Joules compared to the SMX2200RMLV2U's 540 Joules. If surge energy absorption is a key criterion, the CyberPower unit has a significant advantage on this spec.

Can I see documented runtime figures before buying the PR2200RT2UC?

The specifications provided for the PR2200RT2UC do not include runtime figures at full or half load. The SMX2200RMLV2U specifies 10 minutes at full load and 25 minutes at half load. Buyers requiring confirmed runtime data for the CyberPower unit should consult the manufacturer's full datasheet directly.

Which unit supports network management cards or expansion accessories?

The SMX2200RMLV2U includes one Smart-Slot expansion bay, which is APC's interface for optional network management, environmental monitoring, and relay I/O cards. The PR2200RT2UC references cloud management capability, but no expansion card slot is documented in the provided specifications. Buyers requiring on-premises SNMP or integration with a UPS management platform should verify expansion compatibility with CyberPower before purchasing the PR2200RT2UC.



Get a Second Opinion on Your Camera Choice