CyberPower PR2200RTXL2UC vs CyberPower OL2200RTXL2U: Specification Comparison
Both the CyberPower PR2200RTXL2UC and OL2200RTXL2U are 2200 VA, 2U rack-mount UPS units targeting data centers, server rooms, and critical IT infrastructure. The comparison pits a Line Interactive design (PR2200RTXL2UC, 2200 W output, NEMA L5-30P input) against a Double-Conversion Online design (OL2200RTXL2U, 1800 W output, 100–125 VAC input). Both carry a 3-year limited warranty and a $400,000 connected equipment guarantee, making them genuine cross-shop candidates for buyers evaluating power topology against runtime and outlet configuration.
In This Guide
- Which UPS topology and runtime are better suited for sensitive or critical loads?
- How do rated power capacity, outlet configuration, and input requirements compare?
- What management, connectivity, and physical installation differences should installers and IT buyers know?
- Which should you choose: the PR2200RTXL2UC or the OL2200RTXL2U?
- Side-by-Side Specs
- FAQ
Which UPS topology and runtime are better suited for sensitive or critical loads?
The OL2200RTXL2U uses double-conversion (online) topology, meaning the load runs exclusively off conditioned inverter power at all times. This eliminates transfer-time concerns entirely—there is no switching delay to battery. The PR2200RTXL2UC is Line Interactive with a typical transfer time of 4 ms and Automatic Voltage Regulation (double boost, single buck) that handles sags and surges without going to battery at all, but does involve a brief transfer when a true outage occurs.
Runtime figures differ significantly between the two models. At full load the OL2200RTXL2U delivers 8 minutes and 21 minutes at half load, enabled by six 12 V/9 Ah batteries (total 648 Wh capacity against 1800 W rated output). The PR2200RTXL2UC provides 3.2 minutes at full load and 10 minutes at half load from four 12 V/9 Ah batteries (432 Wh against 2200 W rated output). Buyers needing longer ride-through at any load should note that only the OL2200RTXL2U supports up to 10 external battery modules for extended runtime; no equivalent external battery module support is specified for the PR2200RTXL2UC.
How do rated power capacity, outlet configuration, and input requirements compare?
Despite the same 2200 VA nameplate, the two units differ in watt output. The PR2200RTXL2UC is rated at 2200 W (power factor 1.0), while the OL2200RTXL2U is rated at 1800 W—a 400 W gap that matters when sizing against actual load. Buyers running high-density, high-power-factor servers should account for this difference.
Outlet counts and types also diverge. The PR2200RTXL2UC offers 8 total NEMA 5-20R outlets (4 on battery-backed critical load, 4 battery-backed), all behind a 30 A circuit breaker fed by a NEMA L5-30P twist-lock plug. The OL2200RTXL2U provides 7 total outlets: 6× NEMA 5-20R plus 1× L5-20R, with no critical-load vs. full-battery sub-group split specified. The L5-30P input on the PR2200RTXL2UC requires a matching receptacle or PDU port—a facilities consideration absent from the OL2200RTXL2U's standard 100–125 VAC input range.
What management, connectivity, and physical installation differences should installers and IT buyers know?
The PR2200RTXL2UC ships with native cloud connectivity and supports USB, Serial, SNMP, EPO (Emergency Power Off), and cloud management via CyberPower's PowerPanel® Business software. SNMP is included in the base unit, and cloud telemetry is available without an add-on card. The OL2200RTXL2U offers USB (HID) and Serial (RS-232) natively but requires the optional RMCARD205 network management card for SNMP/remote monitoring; no native cloud management is specified.
Both units are 2U rack/tower convertible. The PR2200RTXL2UC measures 434 × 86 × 500 mm and weighs 79.6 lb; the OL2200RTXL2U is physically deeper at 432 × 89 × 600 mm and lighter at 68.2 lb. The 100 mm additional depth of the OL2200RTXL2U may matter in shallow rack enclosures. The PR2200RTXL2UC specifies audible noise at 57.5 dBA at 1 m and thermal dissipation of 135 BTU/hr; equivalent figures are not provided in the OL2200RTXL2U spec set. Battery serviceability differs: the OL2200RTXL2U explicitly supports hot-swap, user-replaceable batteries; the PR2200RTXL2UC spec does not state hot-swap capability.
Which should you choose: the PR2200RTXL2UC or the OL2200RTXL2U?
Our take: The OL2200RTXL2U is the stronger choice when load isolation, zero-transfer-time protection, and runtime extensibility are the priority. Its double-conversion topology ensures loads never see raw utility power, versus the PR2200RTXL2UC's 4 ms transfer time under Line Interactive operation. The OL2200RTXL2U also supports up to 10 external battery modules—no equivalent is specified for the PR2200RTXL2UC—and its hot-swappable batteries reduce planned maintenance windows. However, the PR2200RTXL2UC delivers 2200 W versus 1800 W at the same VA rating, includes native SNMP and cloud management without an add-on card, and provides 8 outlets versus 7. Choose the PR2200RTXL2UC for high-power-factor loads, environments already running PowerPanel® Business, or installations where a 30 A twist-lock input circuit is available. Choose the OL2200RTXL2U for medical, financial, or broadcast environments demanding zero transfer time and where future runtime expansion via external battery modules is likely.
Side-by-Side Comparison
Spec-for-spec, from manufacturer data.
| Specification | CyberPower PR2200RTXL2UC | CyberPower OL2200RTXL2U |
|---|---|---|
| Topology | Line Interactive | Double-Conversion (Online) |
| Capacity (VA) | 2200 VA | 2200 VA |
| Capacity (Watts) | 2200 W | 1800 W |
| Output Power Factor | 1.0 | Not specified |
| Output Voltage | 100/110/120 VAC ±5% | 100/110/115/120/125 VAC ±2% (configurable) |
| Transfer Time | 4 ms typical | Zero (online — no transfer) |
| Runtime at Full Load | 3.2 minutes | 8 minutes |
| Runtime at Half Load | 10 minutes | 21 minutes |
| External Battery Module Support | Not specified | Up to 10 modules |
| Total Outlets | 8× NEMA 5-20R | 6× NEMA 5-20R + 1× L5-20R (7 total) |
| Input Plug | NEMA L5-30P | 100–125 VAC nominal (plug type not specified) |
| Battery | 4× 12V/9Ah Sealed Lead-Acid | 6× 12V/9Ah Sealed Lead-Acid, hot-swappable |
| Typical Recharge Time | 3 hours | Not specified |
| Connectivity (Native) | USB, Serial, SNMP, EPO, Cloud | USB (HID), Serial (RS-232) |
| SNMP / Network Management | Native (included) | Optional RMCARD205 card required |
| Management Software | PowerPanel® Business | Not specified |
| Surge Suppression | 2430 J | Not specified |
| AVR | Double Boost, Single Buck | Not specified (online topology regulates continuously) |
| Dimensions (W×H×D) | 434 × 86 × 500 mm | 432 × 89 × 600 mm |
| Weight | 79.6 lb (36.11 kg) | 68.2 lb (30.93 kg) |
| Audible Noise | 57.5 dBA at 1 m | Not specified |
| Thermal Dissipation | 135 BTU/hr | Not specified |
| Form Factor | 2U Rack/Tower | 2U Rack/Tower |
| Warranty | 3-Year Limited | 3-Year Limited |
| Connected Equipment Guarantee | $400,000 | $400,000 (lifetime) |
| Certifications | UL1778, FCC Class A, CSA C22.2 No.107.3, VCCI | UL1778, CSA C22.2 No.107.3, FCC Part 15 Class A, RoHS |
Frequently Asked Questions
Which should you choose: the PR2200RTXL2UC or the OL2200RTXL2U?
The OL2200RTXL2U is the stronger choice when load isolation, zero-transfer-time protection, and runtime extensibility are the priority. Its double-conversion topology ensures loads never see raw utility power, versus the PR2200RTXL2UC's 4 ms transfer time under Line Interactive operation. The OL2200RTXL2U also supports up to 10 external battery modules—no equivalent is specified for the PR2200RTXL2UC—and its hot-swappable batteries reduce planned maintenance windows. However, the PR2200RTXL2UC delivers 2200 W versus 1800 W at the same VA rating, includes native SNMP and cloud management without an add-on card, and provides 8 outlets versus 7. Choose the PR2200RTXL2UC for high-power-factor loads, environments already running PowerPanel® Business, or installations where a 30 A twist-lock input circuit is available. Choose the OL2200RTXL2U for medical, financial, or broadcast environments demanding zero transfer time and where future runtime expansion via external battery modules is likely.
Which unit is better for servers that cannot tolerate any power interruption during a utility outage?
The OL2200RTXL2U is better suited for that use case. Its double-conversion online topology means the load runs off the inverter continuously—there is no transfer switching when utility power fails. The PR2200RTXL2UC is Line Interactive with a specified 4 ms typical transfer time, which most servers tolerate, but is not zero.
Can either UPS be expanded with external battery modules for longer runtime?
The OL2200RTXL2U specifies support for up to 10 external battery modules, enabling significantly longer runtime beyond its base 8 minutes at full load or 21 minutes at half load. The PR2200RTXL2UC specifications do not mention external battery module support; buyers requiring runtime extensibility should verify with CyberPower before specifying that model.
Do I need to buy a separate network card to get SNMP management on either unit?
The PR2200RTXL2UC includes SNMP, serial, USB, EPO, and cloud management natively—no additional card is required. The OL2200RTXL2U ships with USB (HID) and Serial (RS-232) only; SNMP and remote network management require the separately purchased optional RMCARD205 network management card.
More UPS Comparisons
- CyberPower PR2200RTXL2UC vs APC by Schneider Electric SRT2200RMXLA
- CyberPower PR2200RTXL2UC vs APC by Schneider Electric SRT2200XLA
- CyberPower PR2200RTXL2UC vs APC by Schneider Electric SRT2200RMXLA-NC
- CyberPower PR2200RTXL2UC vs APC by Schneider Electric SMT2200I
- CyberPower PR2200RTXL2UC vs CyberPower OL2K2RTHD
- APC by Schneider Electric SRT2200RMXLA vs CyberPower OL2K2RTHD
UPS Buying Guides
Get a Second Opinion on Your Camera Choice
Share your site layout, coverage goals, and budget. Our team will validate the camera selection, flag anything we would change, and recommend products that match the use case.