CyberPower PR2200RTXL2UC vs APC by Schneider Electric SMT2200I

UPS COMPARISON

CyberPower PR2200RTXL2UC vs APC by Schneider Electric SMT2200I: Specification Comparison

Both the CyberPower PR2200RTXL2UC and the APC Smart-UPS SMT2200I are 2200VA line-interactive sine wave UPS units targeting rack-mounted IT and physical-security infrastructure. The CyberPower is a 120V North American model with a 2U rack/tower form factor and cloud-enabled management, while the APC is a 230V international tower unit with an IEC outlet array and SmartSlot expansion. Despite sharing the same VA class and topology, their voltage regions, outlet standards, and physical formats serve distinct deployment contexts — making this a region- and rack-strategy comparison rather than a straight feature race.



How do these two UPS units compare on real power capacity, runtime, and voltage protection?

Both units are rated at 2200VA, but their power delivery differs in an important way. The CyberPower PR2200RTXL2UC specifies a true 2200W output (power factor 1.0), meaning it can deliver its full watt rating to connected loads. The APC SMT2200I lists 2.2 kVA as its maximum configurable power but does not publish a watt figure or output power factor in the provided specs, so a direct watt-for-watt comparison cannot be made from available data.

On runtime, the PR2200RTXL2UC provides 10 minutes at half load and 3.2 minutes at full load, backed by four 12V/9Ah sealed lead-acid batteries. The SMT2200I does not specify runtime values in the provided specs, nor does it list individual battery size or quantity — only a single RBC55 replacement battery cartridge is referenced, and expected battery life is given as 3–5 years.

For voltage regulation, the PR2200RTXL2UC operates on 120VAC nominal with an input range of 75–149VAC and double-boost/single-buck AVR, widening to an adjustable 70–155VAC. The SMT2200I operates on 230VAC nominal with an input range of 160–286VAC, adjustable to 151–302VAC. Transfer time is 4ms typical for the CyberPower versus 2ms typical for the APC — a measurable difference for sensitive loads. Surge suppression is 2,430J for the PR2200RTXL2UC versus only 365J for the SMT2200I.


Which unit offers more flexibility in outlet configuration, connectivity, and load management?

The PR2200RTXL2UC provides 8 NEMA 5-20R outlets, all battery-backed, with 4 designated for critical load segments, a 10-ft. cord, and a 30A circuit breaker. Its input plug is NEMA L5-30P, targeting North American 120V infrastructure with a 30A feed. This outlet count and segmentation is well suited to rack-dense environments with mixed priority loads.

The SMT2200I offers a different outlet mix: 1x IEC C19, 8x IEC C13, and 2x IEC Jumpers (pass-through). Input connections include IEC-320 C20, Schuko CEE 7/EU1-16P, and British BS1363A — reflecting its multi-region 230V market positioning. The SMT2200I does not specify which outlets are battery-backed versus surge-only from the provided specs.

For connectivity and management, the PR2200RTXL2UC includes USB, serial (1 port), SNMP, EPO, and native cloud integration via PowerPanel® Business software. The SMT2200I provides a SmartSlot interface (1 available) for add-in network management cards, and a multi-function LCD control panel. No native cloud or SNMP capability is listed for the SMT2200I in the provided specs — SNMP would require a separately purchased SmartSlot card.


How do the physical form factors, environmental ratings, certifications, and warranties compare?

The PR2200RTXL2UC is a 2U rack/tower convertible unit measuring 434 x 86 x 500mm (17.1 x 3.4 x 19.7 in.) and weighing 36.11kg (79.6 lbs.). The SMT2200I does not specify a rack height or U-size in the provided specs; its dimensions are 435 x 197 x 544mm with a net weight of 48.8kg — significantly heavier. The SMT2200I's greater width (197mm vs 86mm) and absence of a rack-unit rating strongly suggest it is a tower-only form factor, though this is not explicitly stated in the provided specs.

Operating environment specs are broadly similar: both support 0–95% relative humidity. The PR2200RTXL2UC is rated 32–104°F (0–40°C) operating and up to 9,843 ft. elevation. The SMT2200I is rated 0–40°C operating and up to 3,000 meters (approximately 9,843 ft.) — effectively identical operating ceilings. For storage, the APC unit specifies a lower limit of -15°C and upper of 45°C; the CyberPower specifies 5–113°F (approximately -15–45°C) storage — comparable ranges.

Certifications differ by region. The PR2200RTXL2UC carries UL1778, CSA C22.2 No 107.3, FCC Class A, and VCCI — North American and Japanese market approvals. The SMT2200I carries CE, CSA, EAC, EN/IEC 62040-1, EN/IEC 62040-2, RCM, and VDE — covering European, Australian, and Russian conformance. Warranty terms: both offer 3-year product warranties; the SMT2200I separately limits battery warranty to 2 years and excludes batteries from the main warranty. The PR2200RTXL2UC includes a $400,000 connected equipment guarantee; no equivalent figure is stated for the SMT2200I in the provided specs. Acoustic output is 57.5 dBA for the CyberPower versus 45.0 dBA for the APC — a 12.5 dBA difference that is significant in quiet or shared spaces.


Which should you choose: the PR2200RTXL2UC or the SMT2200I?

Our take: The PR2200RTXL2UC is the stronger choice when the deployment is a North American 120V rack environment requiring native cloud management, maximum surge suppression, and a confirmed 2U rack form factor. Key spec deltas: the CyberPower delivers 2,430J of surge suppression versus the APC's 365J; it ships with a 2U rack-ready chassis versus the SMT2200I's tower-only profile (no rack height specified); and it includes native USB, serial, SNMP, EPO, and cloud connectivity without add-in cards, versus the APC's SmartSlot-dependent SNMP. Conversely, the SMT2200I's 2ms transfer time beats the CyberPower's 4ms, it runs 12.5 dBA quieter (45 vs 57.5 dBA), and it is certified for 230V multi-region deployment across EU, AU, and EAC markets. If the install is 230V international, tower-format, or requires IEC outlet standards, the SMT2200I is the appropriate unit; the PR2200RTXL2UC is not electrically compatible with those environments.


Side-by-Side Comparison

Spec-for-spec, from manufacturer data.

SpecificationCyberPower PR2200RTXL2UCAPC by Schneider Electric SMT2200I
Capacity (VA)2200 VA2200 VA (2.2 kVA)
Capacity (Watts)2200 W— (not specified)
Output Power Factor1.0— (not specified)
TopologyLine InteractiveLine Interactive
WaveformSine WaveSine Wave
Nominal Input Voltage120 VAC230 V
Input Voltage Range75 – 149 VAC160 – 286 V
Transfer Time4 ms typical2 ms typical
Surge Energy Rating2,430 J365 J
Outlets (Total / Battery-backed)8 total / 8 battery-backed9 IEC + 2 jumpers / not specified
Outlet TypeNEMA 5-20R1x IEC C19, 8x IEC C13, 2x IEC Jumpers
Form Factor / Rack HeightRack/Tower, 2U— (rack height not specified)
Dimensions (W x H x D mm)434 x 86 x 500 mm435 x 197 x 544 mm
Net Weight36.11 kg (79.6 lbs.)48.8 kg
Audible Noise57.5 dBA45.0 dBA
Thermal Dissipation135 BTU/hr275 BTU/hr
Battery TypeSealed Lead-Acid, 4x 12V/9AhSealed Lead-Acid, 1x RBC55 cartridge
Runtime at Half Load10 minutes— (not specified)
Runtime at Full Load3.2 minutes— (not specified)
Recharge Time3 hours3 hours
Management / ConnectivityUSB, Serial, SNMP, EPO, Cloud (native)SmartSlot (1 slot; SNMP via add-in card)
Product Warranty3-Year Limited3 years (battery: 2 years, excluded)
Connected Equipment Guarantee$400,000— (not specified)
CertificationsUL1778, FCC Class A, CSA C22.2 No 107.3, VCCICE, CSA, EAC, EN/IEC 62040-1/2, RCM, VDE

Frequently Asked Questions

Which should you choose: the PR2200RTXL2UC or the SMT2200I?

The PR2200RTXL2UC is the stronger choice when the deployment is a North American 120V rack environment requiring native cloud management, maximum surge suppression, and a confirmed 2U rack form factor. Key spec deltas: the CyberPower delivers 2,430J of surge suppression versus the APC's 365J; it ships with a 2U rack-ready chassis versus the SMT2200I's tower-only profile (no rack height specified); and it includes native USB, serial, SNMP, EPO, and cloud connectivity without add-in cards, versus the APC's SmartSlot-dependent SNMP. Conversely, the SMT2200I's 2ms transfer time beats the CyberPower's 4ms, it runs 12.5 dBA quieter (45 vs 57.5 dBA), and it is certified for 230V multi-region deployment across EU, AU, and EAC markets. If the install is 230V international, tower-format, or requires IEC outlet standards, the SMT2200I is the appropriate unit; the PR2200RTXL2UC is not electrically compatible with those environments.

Can I use the PR2200RTXL2UC or SMT2200I outside North America?

No — these units serve different voltage regions and are not interchangeable. The PR2200RTXL2UC is designed exclusively for 120VAC nominal (100–120VAC input, NEMA L5-30P plug) and carries North American certifications (UL1778, FCC Class A, CSA). The SMT2200I is designed for 230VAC nominal (160–286VAC input range) with IEC and Schuko input connections and EU/AU/EAC certifications. Using either unit outside its rated voltage region is outside spec and unsafe.

Which UPS is better for rack installations with multiple servers?

The PR2200RTXL2UC is explicitly rated as a 2U rack/tower unit (434 x 86mm footprint) and is designed for rack integration in North American data closets. The SMT2200I does not specify a rack height or U-size in the provided specs, and its 197mm width suggests it is a tower-format unit. For rack-dense environments requiring 120V power, the PR2200RTXL2UC is the appropriate choice. For 230V environments, the SMT2200I is the regionally correct option, but rack-mounting capability cannot be confirmed from the available specifications.

Does either UPS include built-in network management, or do I need to buy an add-on card?

The PR2200RTXL2UC includes SNMP and cloud connectivity as standard features, managed through CyberPower's PowerPanel® Business software, with no additional card required. The SMT2200I provides a single SmartSlot expansion bay; SNMP network management would require a separately purchased APC SmartSlot network management card, as no native SNMP or cloud capability is listed in the provided specs. The APC does include a multi-function LCD control panel for local monitoring.