CyberPower PR2200RTXL2UC vs APC by Schneider Electric SRT2200RMXLA: Specification Comparison
Both the CyberPower PR2200RTXL2UC and the APC SRT2200RMXLA are 2U rack-mount UPS units rated at 2200VA, targeting server rooms, network closets, and IT infrastructure where power continuity is critical. The comparison centers on topology (Line Interactive vs. Double Conversion Online), real-world output capacity, runtime behavior, outlet configurations, battery extensibility, and management depth — the five axes that most directly affect purchasing decisions in this product class.
In This Guide
- Which UPS topology and true power output better protect critical loads?
- How does runtime compare, and which unit supports extended battery capacity?
- Which unit offers better outlet coverage, connectivity, and remote management?
- Which should you choose: the PR2200RTXL2UC or the SRT2200RMXLA?
- Side-by-Side Specs
- FAQ
Which UPS topology and true power output better protect critical loads?
The PR2200RTXL2UC uses a Line Interactive topology with Automatic Voltage Regulation (double boost, single buck) and delivers 2200W at a power factor of 1.0. Transfer to battery occurs in a typical 4 ms, which is within the hold-up tolerance of most server PSUs. The on-battery waveform is a true sine wave, and output voltage on battery is 100/110/120 VAC ±5%.
The SRT2200RMXLA uses Double Conversion Online topology, meaning the load runs continuously from the inverter and transfer time to battery is effectively 0 ms — there is no transfer event. However, its maximum configurable power is rated at 1800W (kW rating: 1800W), not 2200W, representing a 400W gap versus its VA rating and versus the CyberPower's 2200W output. The SRT2200RMXLA specifies harmonic distortion of less than 2% and a crest factor of 3:1. Bypass type is built-in.
For loads that are sensitive to any transfer gap — medical devices, industrial controllers, or servers with narrow PSU hold-up — the SRT2200RMXLA's zero-transfer online topology is the architectural advantage. For general IT loads where 4 ms transfer is acceptable, the PR2200RTXL2UC delivers 22% more real watts (2200W vs. 1800W) at the same VA rating.
How does runtime compare, and which unit supports extended battery capacity?
The PR2200RTXL2UC specifies runtime of 10 minutes at half load (1100W) and 3.2 minutes at full load (2200W). Its internal battery bank consists of 4 × 12V/9Ah sealed lead-acid cells (total 432 Wh nominal). Recharge time is specified at 3 hours. No external battery extension option is listed in the provided specs.
The SRT2200RMXLA lists a rated battery capacity of 306 VAh (at 72V internal battery string) with a 102W charge power rating. Specific half-load and full-load runtime figures are not provided in the supplied specs. Recharge time is also 3 hours. Critically, the SRT2200RMXLA supports up to 10 external Smart-UPS SRT battery packs (SRT72RMBP), scaling total runtime capacity from 916 VAh (1 pack) to 6,426 VAh (10 packs), making extended runtime deployments feasible within the same product family.
Without runtime figures for the SRT2200RMXLA, a direct minute-for-minute comparison cannot be made. The PR2200RTXL2UC's runtime is fully specified. The SRT2200RMXLA's external battery extensibility is a documented structural advantage for deployments requiring sustained runtime.
Which unit offers better outlet coverage, connectivity, and remote management?
The PR2200RTXL2UC provides 8 total outlets, all NEMA 5-20R, with 4 designated as critical load outlets. Input connection is NEMA L5-30P on a 10 ft. cord, which requires a 30A circuit — an important installation prerequisite. Communication interfaces include USB, serial (1 port), SNMP, EPO (Emergency Power Off), and cloud connectivity. Management is via CyberPower's PowerPanel® Business software. Surge suppression is rated at 2,430 J.
The SRT2200RMXLA provides 7 total outlets: 6 × NEMA 5-20R plus 1 × NEMA L5-20R, on a NEMA 5-20P input plug with a 6 ft. cord. A 20A input circuit is required. Network management card (card types 2 or 3 with environmental monitoring) is listed as optional — it is not included. Audible and visible alarms are described as prioritized by severity. Surge suppression joule rating, serial port count, and EPO support are not stated in the provided specs.
The PR2200RTXL2UC includes cloud and SNMP communication out of the box per spec. The SRT2200RMXLA's network card is optional; buyers must factor in add-on cost if remote SNMP management is required. The PR2200RTXL2UC's L5-30P plug requires a 30A circuit whereas the SRT2200RMXLA's 5-20P requires only a standard 20A circuit — a meaningful installation difference.
Which should you choose: the PR2200RTXL2UC or the SRT2200RMXLA?
Our take: The SRT2200RMXLA is the stronger choice when zero transfer time, external battery extensibility, and a standard 20A input circuit are the governing requirements. Its Double Conversion Online topology eliminates the 4 ms transfer event present in the PR2200RTXL2UC, and its support for up to 10 external battery packs (scaling to 6,426 VAh) makes it suitable for extended-runtime deployments. However, the SRT2200RMXLA's actual power output is 1800W versus the PR2200RTXL2UC's 2200W — a 400W deficit at the same VA rating — and its network management card is an optional add-on, not included. The PR2200RTXL2UC includes cloud and SNMP connectivity as standard, carries a 3-year warranty and $400,000 connected equipment guarantee per spec, and delivers full rated watts. Choose the SRT2200RMXLA for always-on critical infrastructure with extension runtime needs; choose the PR2200RTXL2UC for higher real-watt output and included management features on a 30A circuit.
Side-by-Side Comparison
Spec-for-spec, from manufacturer data.
| Specification | CyberPower PR2200RTXL2UC | APC by Schneider Electric SRT2200RMXLA |
|---|---|---|
| VA Rating | 2200 VA | 2200 VA |
| True Power Output (W) | 2200 W | 1800 W |
| Output Power Factor | 1.0 | — |
| UPS Topology | Line Interactive | Double Conversion Online |
| Transfer Time | 4 ms (typical) | 0 ms (online) |
| Waveform | Sine Wave | Sine Wave |
| Input Plug | NEMA L5-30P (30A) | NEMA 5-20P (20A) |
| Cord Length | 10 ft. | 6 ft. (1.83 m) |
| Total Outlets | 8 × NEMA 5-20R | 6 × NEMA 5-20R + 1 × NEMA L5-20R |
| Runtime at Half Load | 10 min. | — |
| Runtime at Full Load | 3.2 min. | — |
| Battery Recharge Time | 3 hours | 3 hours |
| External Battery Extension | — | Up to 10 × SRT72RMBP (916–6,426 VAh) |
| SNMP / Network Mgmt | Included | Optional (add-on card) |
| Surge Suppression | 2,430 J | — |
| Acoustic Noise | 57.5 dBA | 55 dBA |
| Heat Dissipation | 135 BTU/hr | 535 BTU/hr |
| Form Factor / Rack Height | Rack/Tower 2U | Rack 2U |
| Weight | 79.6 lbs. (36.11 kg) | 55.01 lbs. (24.95 kg) |
| Product Warranty | 3-Year Limited | — |
| Connected Equipment Guarantee | $400,000 | — |
Frequently Asked Questions
Which should you choose: the PR2200RTXL2UC or the SRT2200RMXLA?
The SRT2200RMXLA is the stronger choice when zero transfer time, external battery extensibility, and a standard 20A input circuit are the governing requirements. Its Double Conversion Online topology eliminates the 4 ms transfer event present in the PR2200RTXL2UC, and its support for up to 10 external battery packs (scaling to 6,426 VAh) makes it suitable for extended-runtime deployments. However, the SRT2200RMXLA's actual power output is 1800W versus the PR2200RTXL2UC's 2200W — a 400W deficit at the same VA rating — and its network management card is an optional add-on, not included. The PR2200RTXL2UC includes cloud and SNMP connectivity as standard, carries a 3-year warranty and $400,000 connected equipment guarantee per spec, and delivers full rated watts. Choose the SRT2200RMXLA for always-on critical infrastructure with extension runtime needs; choose the PR2200RTXL2UC for higher real-watt output and included management features on a 30A circuit.
Is the PR2200RTXL2UC or SRT2200RMXLA better for servers that cannot tolerate any power interruption?
The SRT2200RMXLA is better for that use case. Its Double Conversion Online topology means the load runs continuously from the inverter — there is no transfer event. The PR2200RTXL2UC is Line Interactive with a specified typical transfer time of 4 ms, which is within tolerance for most server power supplies but is not zero.
Can I add external battery packs to either unit to extend runtime during outages?
Based on the provided specs, only the SRT2200RMXLA explicitly supports external battery extension — up to 10 SRT72RMBP battery packs, scaling from 916 VAh to 6,426 VAh. No external battery extension option is listed in the PR2200RTXL2UC specifications.
Do both units include SNMP and remote management out of the box?
The PR2200RTXL2UC includes USB, serial, SNMP, EPO, and cloud connectivity per its specs, along with PowerPanel® Business software. The SRT2200RMXLA lists a network management card (type 2 or 3) as optional, meaning SNMP capability is not included and must be purchased separately.
More UPS Comparisons
- CyberPower PR2200RTXL2UC vs APC by Schneider Electric SRT2200XLA
- CyberPower PR2200RTXL2UC vs APC by Schneider Electric SRT2200RMXLA-NC
- CyberPower PR2200RTXL2UC vs APC by Schneider Electric SMT2200I
- CyberPower PR2200RTXL2UC vs CyberPower OL2K2RTHD
- CyberPower PR2200RTXL2UC vs CyberPower OL2200RTXL2U
- APC by Schneider Electric SRT2200RMXLA vs CyberPower OL2K2RTHD