CyberPower PR2200LCD vs APC by Schneider Electric SRT2200RMXLA-NC: Specification Comparison

Both products are 2200VA uninterruptible power supplies operating at 120V, making them a natural cross-shop pair for buyers sizing a mid-range UPS for IT or AV loads. The CyberPower PR2200LCD is a tower-form line-interactive unit with AVR, while the APC SRT2200RMXLA-NC is a 2U rack-mount double-conversion online UPS. The comparison covers topology and output quality, physical deployment and environmental fit, and battery runtime expandability — the three axes that most directly drive a purchase decision at this VA class.



Which unit delivers cleaner, more protected power output?

The APC SRT2200RMXLA-NC uses a double-conversion online topology, meaning the load runs continuously off the inverter with the raw utility input isolated. This eliminates all input voltage and frequency disturbances before they reach connected equipment. Its specs document a harmonic distortion figure of less than 2% THD and a crest factor rating of 3:1, with output frequency held at 50/60 Hz ±3 Hz synchronized to mains during normal operation. The SRT2200RMXLA-NC also lists a built-in bypass for servicing without dropping the load.

The CyberPower PR2200LCD is specified as a sinewave output unit with AVR (Automatic Voltage Regulation) and output voltage of 120 VAC ±5%. Its provided specifications do not state a UPS topology label (line-interactive is implied by the AVR and tower form factor for this product line), and no THD or crest-factor figure appears in the supplied spec sheet. For loads sensitive to waveform quality or frequency excursions — active power factor correction power supplies in servers, medical-adjacent equipment, or precision lab gear — the documented double-conversion architecture and sub-2% THD of the APC unit represent a meaningful, verifiable difference.


How do form factor, weight, and operating environment compare for installation?

The CyberPower PR2200LCD is a tower unit measuring 7.7 × 17 × 20.2 in (W×H×D) and weighing 116 lb. It is floor- or shelf-standing and does not occupy rack space. Its operating temperature range is 32–104°F (0–40°C); no humidity or altitude specification is provided in the supplied data.

The APC SRT2200RMXLA-NC is a 2U rack-mount unit specified for horizontal mounting in a standard rack. Its listed dimensions are 3.35 in height (the rack dimension), and it weighs 55.01 lb — less than half the CyberPower's 116 lb. APC's environmental envelope is fully documented: 0–95% relative humidity (non-condensing), operating altitude up to 10,000 ft, storage altitude up to 50,000 ft, ambient storage temperature –4 to 122°F (–20 to 50°C), and an acoustic noise level of 55 dBA with a heat dissipation figure of 535 Btu/h. The PR2200LCD spec sheet provides none of those environmental parameters. Buyers deploying into high-altitude facilities, dense rack environments, or data centers requiring ASHRAE compliance documentation will find the APC spec sheet more immediately useful.


Which unit offers greater battery capacity, runtime scalability, and replacement options?

The APC SRT2200RMXLA-NC ships with one internal battery module (APCRBC141 / SRT72RMBPUS), delivering 306 VAh of runtime capacity at a 72V battery bus. The unit supports up to 10 external SRT72RMBP battery packs, scaling runtime from the base 306 VAh up to a documented 6,426 VAh — a roughly 21× extension. Recharge time from full discharge is specified at 3 hours, and battery life is listed at 3–5 years. The extendable runtime architecture is confirmed in the spec (Extendable Run Time: 1).

The CyberPower PR2200LCD specifications do not disclose battery capacity in VAh or Ah, recharge time, runtime extendability, battery bus voltage, or rated battery life. The spec sheet confirms a sealed lead-acid battery type and a 3-year limited warranty covering the unit, but no expansion path is documented. Buyers who anticipate needing extended runtime for longer outages — such as edge sites without generator backup — will find the APC's documented scalability and published runtime math directly actionable, while the CyberPower's runtime characteristics cannot be evaluated from the provided data.


Which should you choose: the PR2200LCD or the SRT2200RMXLA-NC?

Our take: The SRT2200RMXLA-NC is the stronger choice when load protection quality, environmental documentation, and runtime scalability are the primary criteria. Its double-conversion online topology with less-than-2% THD directly outspecifies the PR2200LCD's undisclosed topology and waveform figures for sensitive server or precision loads. At 55.01 lb versus 116 lb, it installs in a 2U rack slot rather than consuming floor space, and its full environmental envelope — 0–95% RH, 10,000 ft operating altitude, 55 dBA acoustic level — supports data-center and high-altitude deployments the PR2200LCD spec sheet cannot validate. The SRT's battery platform scales from 306 VAh to 6,426 VAh via up to 10 external packs, versus no documented expansion path for the CyberPower. The PR2200LCD is worth considering for a tower-only deployment where rack space is unavailable and the 3-year warranty and 10-outlet count are valued over topology documentation.


Side-by-Side Comparison

Spec-for-spec, from manufacturer data.

SpecificationCyberPower PR2200LCDAPC by Schneider Electric SRT2200RMXLA-NC
VA Rating2200VA2200VA
Watt Rating1800W
Form FactorTower2U Rack-Mount
UPS TopologyDouble Conversion Online
Waveform OutputSine waveSine wave
Output Voltage120 VAC ±5%120V
Input Voltage120 VAC120V
Input ConnectorNEMA 5-20P
Output Outlets10(6) NEMA 5-20R + (1) NEMA L5-20R
Harmonic Distortion (THD)< 2%
Crest Factor3:1
Battery TypeSealed Lead-AcidLead-Acid
Battery Capacity306 VAh (base)
Runtime ExpandableYes, up to 6,426 VAh (10 ext. packs)
Recharge Time3 hours
Battery Life3–5 years
Weight116 lb55.01 lb (24.95 kg)
Operating Temp32–104°F (0–40°C)
Operating Humidity0–95% non-condensing
Operating Altitude0–10,000 ft
Acoustic Level55 dBA
Heat Dissipation535 Btu/h
BypassBuilt-in bypass
Warranty3 Year Limited
ComplianceUL1778, RoHSIP20

Frequently Asked Questions

Which should you choose: the PR2200LCD or the SRT2200RMXLA-NC?

The SRT2200RMXLA-NC is the stronger choice when load protection quality, environmental documentation, and runtime scalability are the primary criteria. Its double-conversion online topology with less-than-2% THD directly outspecifies the PR2200LCD's undisclosed topology and waveform figures for sensitive server or precision loads. At 55.01 lb versus 116 lb, it installs in a 2U rack slot rather than consuming floor space, and its full environmental envelope — 0–95% RH, 10,000 ft operating altitude, 55 dBA acoustic level — supports data-center and high-altitude deployments the PR2200LCD spec sheet cannot validate. The SRT's battery platform scales from 306 VAh to 6,426 VAh via up to 10 external packs, versus no documented expansion path for the CyberPower. The PR2200LCD is worth considering for a tower-only deployment where rack space is unavailable and the 3-year warranty and 10-outlet count are valued over topology documentation.

Can I rack-mount the CyberPower PR2200LCD alongside servers in a standard equipment rack?

No. Based on the provided specifications, the PR2200LCD is a tower form factor with dimensions of 7.7 × 17 × 20.2 in and no rack-mount designation. The APC SRT2200RMXLA-NC is explicitly specified as a 2U rack-mount unit for horizontal installation in a standard rack.

Which UPS supports longer runtimes if I need to ride through extended outages?

The APC SRT2200RMXLA-NC supports up to 10 external SRT72RMBP battery packs, scaling documented capacity from 306 VAh to 6,426 VAh. The CyberPower PR2200LCD specifications do not disclose battery capacity, runtime, or any external battery expansion capability, so a direct runtime comparison cannot be made from the supplied data.

Is the APC SRT2200RMXLA-NC suitable for powering servers with active power factor correction (APFC) power supplies?

The SRT2200RMXLA-NC's double-conversion online topology with a documented crest factor of 3:1 and less-than-2% harmonic distortion is compatible with the APFC power supplies found in modern servers. The PR2200LCD is specified as sinewave output, which is also generally compatible with APFC loads, but no THD or crest-factor figure is provided in its spec sheet to confirm the same level of detail.