CyberPower PR1000RTXL2UC vs APC by Schneider Electric SURT1000RMXLI

UPS COMPARISON

CyberPower PR1000RTXL2UC vs APC by Schneider Electric SURT1000RMXLI: Specification Comparison

Both the CyberPower PR1000RTXL2UC and the APC Smart-UPS RT SURT1000RMXLI are 1000VA, 2U rack-mount UPS units targeting server rooms, network closets, and critical IT infrastructure. The comparison spans topology, regional voltage targeting, runtime and power delivery, surge protection, communications, and management capabilities — the core decision axes for installers and IT buyers selecting a 1000VA rack UPS for North American or international deployments.



Which UPS topology and runtime actually protects your critical load better?

The PR1000RTXL2UC uses a Line Interactive topology with Automatic Voltage Regulation (AVR) providing double-boost and single-buck correction, delivering a 1000W output at a 1.0 power factor with a typical transfer time of 4ms to battery. At half load (500W) it provides 20 minutes of runtime; at full load (1000W), 8 minutes. Waveform is sine wave both on-line and on-battery.

The SURT1000RMXLI uses a Double Conversion Online topology, meaning the load runs continuously off the inverter with zero transfer time — the inverter output is always active. Its rated output is 700W at 1000VA, reflecting a 0.7 power factor. Runtime figures are not specified in the provided data. Harmonic distortion is specified at less than 3%, and the crest factor is 3:1. A built-in bypass is included.

For applications requiring true zero transfer time and tighter output voltage conditioning, double conversion online (SURT1000RMXLI) is the architectural advantage. For applications where 4ms transfer is acceptable and full 1000W output capacity matters, the PR1000RTXL2UC delivers 43% more watts from the same VA rating.


Which unit fits your input voltage, regional power environment, and physical installation requirements?

The PR1000RTXL2UC is designed exclusively for North American power: nominal input 120VAC, input range 100–125VAC, with a NEMA 5-15P plug and 10 ft. cord. It accepts a wide operating input range of 75–149VAC (adjustable 70–155VAC) via AVR. It provides 8 NEMA 5-15R outlets (all battery-backed, 4 designated critical load), protected by a 15A circuit breaker. Surge suppression is rated at 2430 J. Heat dissipation is 48.6 BTU/hr. Operating temperature is 32–104°F (0–40°C).

The SURT1000RMXLI is designed for international 230V markets: main input 230V, accepting 220V and 240V alternatives, input range 160–280V, via IEC 60320 C14 inlet. Output connections are 6 IEC 60320 C13 and 2 IEC jumper outlets. Heat dissipation is substantially higher at 324 BTU/hr, consistent with the double-conversion topology's continuous conversion losses. Operating temperature is 0–40°C; acoustic level is specified at 50 dBA. IP protection is IP20.

These two units target entirely different electrical infrastructure: the PR1000RTXL2UC is a North American 120V device; the SURT1000RMXLI is a 230V international device. No cross-regional deployment is supported without infrastructure changes. Physical depth differs: 411mm (PR1000RTXL2UC) vs 483mm (SURT1000RMXLI) — buyers should verify rack depth clearance for the APC unit.


Which unit offers more complete management, communications, and software integration for IT operations?

The PR1000RTXL2UC provides USB, Serial (1 port), SNMP, Relay, and EPO (Emergency Power Off) communication interfaces, plus a dry contact port. It includes a multifunction LCD display and is bundled with PowerPanel® Business management software. Cloud connectivity is indicated in the product name and SKU. Certifications include UL1778, CSA C22.2 No 107.3, FCC Class B, VCCI, RoHS, and DOE Compliance. A $400,000 Connected Equipment Guarantee is included. Warranty is 3 years.

The SURT1000RMXLI provides 1 free expansion slot for optional network management cards — specific interfaces (USB, serial, SNMP) are not enumerated in the provided specifications beyond the slot. No bundled management software is specified. Certifications listed are C-Tick, CE, GOST, VDE, and UK PSTI, consistent with international/European market compliance. Battery life is specified at 3–5 years. No Connected Equipment Guarantee figure is provided in the specifications.

The PR1000RTXL2UC ships with a more fully specified out-of-box communications suite including SNMP, EPO, and PowerPanel® Business software. The SURT1000RMXLI's management capability depends on which optional NMC is installed in its expansion slot — a cost and configuration variable not resolved by the provided specs.


Which should you choose: the PR1000RTXL2UC or the SURT1000RMXLI?

Our take: The PR1000RTXL2UC is the stronger choice when deploying in North American 120V environments where full 1000W output capacity, a comprehensive out-of-box communications stack, and lower heat dissipation are priorities. It delivers 1000W versus the SURT1000RMXLI's 700W ceiling — a 43% capacity advantage from the same VA rating — and ships with SNMP, EPO, USB, Serial, dry contact, PowerPanel® Business software, and a $400,000 Connected Equipment Guarantee without additional hardware. Heat output is dramatically lower at 48.6 BTU/hr versus 324 BTU/hr. However, the SURT1000RMXLI is the correct choice for 230V international deployments where zero transfer time (double-conversion online topology) is architecturally required, or where harmonic distortion below 3% and a 3:1 crest factor matter to the protected load. These units are not interchangeable across voltage regions.


Side-by-Side Comparison

Spec-for-spec, from manufacturer data.

SpecificationCyberPower PR1000RTXL2UCAPC by Schneider Electric SURT1000RMXLI
Rated Capacity (VA)1000 VA1000 VA
Rated Capacity (W)1000 W700 W
Output Power Factor1.00.7 (implied)
TopologyLine InteractiveDouble Conversion Online
WaveformSine WaveSine Wave
Transfer Time4 ms typicalZero (online)
Nominal Input Voltage120 VAC230 V
Input Voltage Range75–149 VAC160–280 V
Input ConnectionNEMA 5-15P, 10 ft cordIEC 60320 C14
Outlets8x NEMA 5-15R (all battery-backed)6x IEC C13 + 2x IEC Jumpers
Surge Suppression2430 J420 J
CommunicationsUSB, Serial, SNMP, Relay, EPO, Dry Contact1 expansion slot (card not specified)
Management SoftwarePowerPanel® BusinessNot specified
Runtime at Half Load20 min
Runtime at Full Load8 min
Heat Dissipation48.6 BTU/hr324 BTU/hr
Battery Recharge Time3 hours3 hours
Rack Height2U2U
Depth411 mm483 mm
Operating Temperature0–40 °C0–40 °C
Warranty3-Year LimitedNot specified
Connected Equipment Guarantee$400,000
Harmonic DistortionLess than 3%
Acoustic Level50 dBA
CertificationsUL1778, CSA, FCC Class B, RoHS, DOEC-Tick, CE, GOST, VDE, UK PSTI

Frequently Asked Questions

Which should you choose: the PR1000RTXL2UC or the SURT1000RMXLI?

The PR1000RTXL2UC is the stronger choice when deploying in North American 120V environments where full 1000W output capacity, a comprehensive out-of-box communications stack, and lower heat dissipation are priorities. It delivers 1000W versus the SURT1000RMXLI's 700W ceiling — a 43% capacity advantage from the same VA rating — and ships with SNMP, EPO, USB, Serial, dry contact, PowerPanel® Business software, and a $400,000 Connected Equipment Guarantee without additional hardware. Heat output is dramatically lower at 48.6 BTU/hr versus 324 BTU/hr. However, the SURT1000RMXLI is the correct choice for 230V international deployments where zero transfer time (double-conversion online topology) is architecturally required, or where harmonic distortion below 3% and a 3:1 crest factor matter to the protected load. These units are not interchangeable across voltage regions.

Can I use the SURT1000RMXLI in the United States on standard 120V outlets?

No. The SURT1000RMXLI is designed for 230V input (accepting 220V–240V) via an IEC 60320 C14 inlet. Its input voltage range is specified as 160–280V. It is not compatible with North American 120V infrastructure without a step-up transformer, which is outside the scope of these specifications.

Does the SURT1000RMXLI provide longer runtime than the PR1000RTXL2UC?

Runtime figures for the SURT1000RMXLI are not provided in the available specifications. The PR1000RTXL2UC is rated at 20 minutes at half load (500W) and 8 minutes at full load (1000W). A direct runtime comparison cannot be made from the provided data.

Which unit is better for protecting sensitive electronics that are sensitive to power transfer gaps?

The SURT1000RMXLI uses a double conversion online topology, meaning the load runs continuously off the inverter with effectively zero transfer time. The PR1000RTXL2UC is line interactive with a specified typical transfer time of 4ms. For loads that cannot tolerate any transfer gap — certain medical, industrial control, or high-sensitivity networking equipment — the double-conversion online architecture of the SURT1000RMXLI is the appropriate topology, provided the deployment is on a 230V circuit.