APC by Schneider Electric SYH6K6RMT vs APC by Schneider Electric SYH6K6RMI

UPS COMPARISON

APC by Schneider Electric SYH6K6RMT vs APC by Schneider Electric SYH6K6RMI: Specification Comparison

Both the SYH6K6RMT and SYH6K6RMI are APC Symmetra RM rack-mountable, double-conversion online UPS systems rated at 6 kVA / 4200 W, targeting the same power-protection tier in data center and critical-infrastructure rack deployments. The comparison centers on three decision-relevant axes: output connections and regional voltage compatibility, runtime and battery characteristics, and management interface plus environmental ratings. Neither unit is an accessory or a different device class; cross-shopping between them is appropriate.



Which model fits your regional outlet standard and load-connection requirements?

The SYH6K6RMT is configured for North American installations. Its input arrives via a single NEMA L6-30P (30 A, 208 V) plug, and its output bank delivers (2) NEMA L6-20R plus (1) NEMA L6-30R receptacles — a mix suited to 20 A and 30 A North American equipment. The spec sheet also notes it is configurable for 208 V or 240 V nominal output, giving some flexibility within the North American split-phase environment.

The SYH6K6RMI uses a hard-wire 3-wire input (no plug specified in the provided specs) and routes output through (8) IEC 320 C13 plus (2) IEC 320 C19 receptacles — the international standard form factors used throughout Europe, Asia-Pacific, and global data centers. This outlet configuration directly supports C14 and C20 power cords common on international server and network hardware. The SYH6K6RMT specs do not list IEC outlets, and the SYH6K6RMI specs do not list NEMA outlets, making outlet compatibility a hard regional differentiator rather than a preference.


How do the two models compare on runtime, battery configuration, and recharge behavior?

The SYH6K6RMI provides manufacturer-stated runtime figures: 12.7 minutes at full load (4200 W) and 30.3 minutes at half load (2100 W). It also specifies Emergency Power Off (EPO) support. The SYH6K6RMT specs do not include runtime figures at full or half load, so a direct runtime comparison at specific loads cannot be made from the provided data.

Both units share the same replacement battery cartridge (SYBT2) and the same sealed lead-acid battery chemistry. The SYH6K6RMT specs additionally state: 3 battery modules included, 0 empty battery slots, a typical recharge time of 4 hours, a battery charge power of 458 W, and a battery life of 3–5 years. The SYH6K6RMI specs describe the battery as 'maintenance-free sealed Lead-Acid with suspended electrolyte: leakproof' but do not specify recharge time, battery count, or battery life in the provided data. Extendable run time is confirmed for the SYH6K6RMT (spec value: 1); the SYH6K6RMI specs do not state this explicitly.


What management interfaces and environmental operating parameters does each model support?

The SYH6K6RMI specifies a DB-9 RS-232 serial interface plus an RJ-45 10Base-T Ethernet port supporting web, SNMP, and Telnet management — a meaningful network-management capability for remote monitoring in managed data centers. The SYH6K6RMT lists a multi-function LCD status and control console as its control panel; the provided specs do not list a network management card or Ethernet interface for that model.

On operating environment, the SYH6K6RMT provides more granular data: 0–10,000 ft operating altitude, 0–50,000 ft storage altitude, 60 dBA acoustic output, and 1,771 Btu/h heat dissipation. Input power factor at full load is 0.98, and total harmonic distortion is less than 5% at full load. Efficiency at full load is stated at 89%. The SYH6K6RMI specifies an operating temperature of 0–40 °C and storage temperature of -15–45 °C; the SYH6K6RMT specifies storage temperature of -15–45 °C (matching) but does not separately state an upper operating temperature limit in the provided specs. Neither altitude nor acoustic data is present in the SYH6K6RMI specs.


Which should you choose: the SYH6K6RMT or the SYH6K6RMI?

Our take: The SYH6K6RMT is the stronger choice when deploying in a North American 208 V environment where NEMA L6-series outlets are required and detailed battery and electrical efficiency data matter most. Key spec deltas: (1) outlet format — SYH6K6RMT outputs NEMA L6-20R/L6-30R versus SYH6K6RMI's IEC 320 C13/C19, making them non-interchangeable by region; (2) electrical transparency — SYH6K6RMT documents 89% full-load efficiency, <5% THD, and 0.98 input power factor, none of which appear in the SYH6K6RMI provided specs; (3) management — SYH6K6RMI specifies an RJ-45 Ethernet port with SNMP/web/Telnet, a capability not listed for the SYH6K6RMT. Choose the SYH6K6RMI for international IEC-outlet data centers requiring native network management; choose the SYH6K6RMT for North American rack environments where outlet compatibility and documented electrical characteristics take priority.


Side-by-Side Comparison

Spec-for-spec, from manufacturer data.

SpecificationAPC by Schneider Electric SYH6K6RMTAPC by Schneider Electric SYH6K6RMI
SKUSYH6K6RMTSYH6K6RMI
Rated capacity (VA)6000 VA6000 VA
Output power (W)4200 W4200 W
UPS topologyDouble Conversion Online
WaveformSine wave
Input voltage208 V
Output voltage208 V (configurable 208/240 V)
Input connectionNEMA L6-30P (30 A)Hard Wire 3-wire
Output connections(2) NEMA L6-20R, (1) NEMA L6-30R(8) IEC 320 C13, (2) IEC 320 C19
Emergency Power Off (EPO)Yes
Network management interfaceRJ-45 10Base-T (web/SNMP/Telnet), DB-9 RS-232
Runtime at full load12.7 min
Runtime at half load30.3 min
Battery typeLead-AcidMaintenance-free sealed Lead-Acid (suspended electrolyte, leakproof)
Replacement batterySYBT2SYBT2
Battery recharge time4 h
Battery life3–5 years
Efficiency at full load89%
Input power factor at full load0.98
Total harmonic distortion< 5% at full load
Acoustic level60 dBA
Heat dissipation1771 Btu/h
Form factorRack-mountable, 8URack-mountable
Dimensions14.02 in (35.6 cm) depth stated482.6 x 730.3 x 355.6 mm (W x D x H)
Weight294.63 lb (133.64 kg)
Operating temperature0–40 °C
Storage temperature-15–45 °C-15–45 °C
Operating relative humidity0–95%0–95%
Operating altitude0–10,000 ft
ColorBlackBlack

Frequently Asked Questions

Which should you choose: the SYH6K6RMT or the SYH6K6RMI?

The SYH6K6RMT is the stronger choice when deploying in a North American 208 V environment where NEMA L6-series outlets are required and detailed battery and electrical efficiency data matter most. Key spec deltas: (1) outlet format — SYH6K6RMT outputs NEMA L6-20R/L6-30R versus SYH6K6RMI's IEC 320 C13/C19, making them non-interchangeable by region; (2) electrical transparency — SYH6K6RMT documents 89% full-load efficiency, <5% THD, and 0.98 input power factor, none of which appear in the SYH6K6RMI provided specs; (3) management — SYH6K6RMI specifies an RJ-45 Ethernet port with SNMP/web/Telnet, a capability not listed for the SYH6K6RMT. Choose the SYH6K6RMI for international IEC-outlet data centers requiring native network management; choose the SYH6K6RMT for North American rack environments where outlet compatibility and documented electrical characteristics take priority.

Can I use the SYH6K6RMT or SYH6K6RMI outside the United States?

Based on the provided specs, the SYH6K6RMT uses a NEMA L6-30P input plug and NEMA L6-series output receptacles, which are North American standards and are not compatible with international IEC power cords without adapters. The SYH6K6RMI uses a hard-wire 3-wire input and IEC 320 C13/C19 output receptacles, which are internationally standard. For deployments outside North America, the SYH6K6RMI is the appropriate choice based on outlet specification alone.

Which model supports network-based monitoring and remote management?

The SYH6K6RMI explicitly lists an RJ-45 10Base-T Ethernet interface supporting web, SNMP, and Telnet management, plus a DB-9 RS-232 serial port, in its provided specifications. The SYH6K6RMT specs list only a multi-function LCD control console; no network management card or Ethernet port is specified in the provided data for that model. If remote SNMP or web-based monitoring is a requirement, the SYH6K6RMI has a confirmed interface; the SYH6K6RMT cannot be confirmed to offer this from the specs provided.

How long will the SYH6K6RMI run on battery at full load, and is similar data available for the SYH6K6RMT?

The SYH6K6RMI specs state 12.7 minutes at full load (4200 W) and 30.3 minutes at half load (2100 W). The SYH6K6RMT provided specifications do not include runtime figures at any load level, so a direct comparison cannot be made from the available data. Both models use the same SYBT2 replacement battery cartridge; the SYH6K6RMT specs additionally note a 4-hour typical recharge time and a 3-5 year battery life, which are not stated in the SYH6K6RMI provided specs.