APC by Schneider Electric SRT10KXLT-5KTF2 vs Vertiv GXT5-10KHVRT5UXLN: Specification Comparison
Both the APC Smart-UPS SRT10KXLT-5KTF2 and the Vertiv GXT5-10KHVRT5UXLN are 10 kVA / 10,000 W online double-conversion UPS units designed for rackmount data center or server room deployment. The APC unit ships with two integrated 208/240 V to 120 V step-down transformers, giving it a mixed-voltage output profile, while the Vertiv unit is a native 208 V class device with user-configurable output and a factory-installed SNMP/web card. The comparison centers on input flexibility, output wiring and management capability.
In This Guide
- How do input voltage range and output wiring differ between the two units?
- Which unit delivers better runtime efficiency and what certifications does each carry?
- How do the management and monitoring capabilities compare between the two UPS models?
- Which should you choose: the SRT10KXLT-5KTF2 or the GXT5-10KHVRT5UXLN?
- Side-by-Side Specs
- FAQ
How do input voltage range and output wiring differ between the two units?
The APC SRT10KXLT-5KTF2 accepts a wide 100–275 V input range across a 40–70 Hz window, making it tolerant of poor utility power and usable across multiple international voltage environments. Its output spans 120–240 V, enabled by the two bundled 5 kVA step-down transformers, allowing a single UPS to simultaneously serve both 120 V North American loads and 208/240 V equipment.
The Vertiv GXT5-10KHVRT5UXLN is engineered for a typical 208 VAC input with a 176–288 VAC operational range. Output voltage is user-configurable among 200, 208, 220, 230, and 240 VAC. Wiring is hardwired in and out, supplemented by two L6-20R and two L6-30R receptacles. No step-down transformer capability is specified, so 120 V loads would require external transformation. Buyers with mixed 120 V / 208 V equipment racks should weigh this carefully.
Which unit delivers better runtime efficiency and what certifications does each carry?
The Vertiv GXT5-10KHVRT5UXLN publishes explicit efficiency figures: up to 98% in Active ECO Mode and up to 95% in on-line double-conversion mode. ENERGY STAR 2.0 certification, UL1778, c-UL, RoHS2, and REACH listings are stated. Higher efficiency directly reduces heat load and operating cost over the unit's lifecycle.
The APC SRT10KXLT-5KTF2 specifications provided do not include an efficiency percentage or ENERGY STAR certification status. The specs do confirm a 2% output voltage THD, a 3:1 crest factor, and a 55 dB noise level, but no on-line or ECO-mode efficiency figure is given. Buyers for whom efficiency ratings or green-building compliance matter should note the Vertiv's documented 95–98% figure versus the APC's unspecified efficiency in the data provided.
How do the management and monitoring capabilities compare between the two UPS models?
The Vertiv GXT5-10KHVRT5UXLN ships with a factory pre-installed Liebert IntelliSlot RDU120 SNMP/web card, enabling SNMP and web management out of the box. Additional interfaces include USB, RS485, RS232, a terminal block, and an external battery connector. A full-color graphic LCD with gravity-sensing orientation provides local status display. Serial out-of-band management is also supported. No additional card purchase is required for network integration.
The APC SRT10KXLT-5KTF2 specifications confirm web-based management and an audible alarm, but do not detail the physical interface set, whether a network management card is pre-installed or sold separately, or what protocols are supported. The Smart-UPS SRT platform generally supports APC's NMC ecosystem, but those details are absent from the supplied spec sheet and cannot be assumed here.
Which should you choose: the SRT10KXLT-5KTF2 or the GXT5-10KHVRT5UXLN?
Our take: The SRT10KXLT-5KTF2 is the stronger choice when a facility must simultaneously power both 120 V and 208/240 V equipment from a single 10 kVA UPS, because the two bundled step-down transformers are a hardware capability the GXT5-10KHVRT5UXLN does not offer per the supplied specs. The APC unit also accepts a wider input range (100–275 V vs. 176–288 V), providing greater tolerance for unstable utility power. Conversely, the GXT5-10KHVRT5UXLN holds measurable advantages where efficiency and compliance matter: it documents up to 98% ECO-mode / 95% on-line efficiency and carries ENERGY STAR 2.0, UL1778, and RoHS2 listings, none of which appear in the APC spec set provided. The Vertiv also ships with an SNMP/web card pre-installed versus the APC's undetailed management interface. Choose the APC for mixed-voltage rack environments; choose the Vertiv for efficiency-rated, single-voltage 208 V deployments requiring out-of-the-box network management.
Side-by-Side Comparison
Spec-for-spec, from manufacturer data.
| Specification | APC by Schneider Electric SRT10KXLT-5KTF2 | Vertiv GXT5-10KHVRT5UXLN |
|---|---|---|
| Topology | Double-conversion (Online) | On-line double conversion |
| Power Rating (VA) | 10,000 VA | 10,000 VA |
| Power Rating (W) | 10,000 W | 10,000 W |
| Input Voltage Range | 100–275 V | Typical 208 VAC / Range 176–288 VAC |
| Input Frequency | 40–70 Hz | — |
| Output Voltage | 120–240 V (via step-down transformers) | 200/208/220/230/240 VAC (user-configurable) |
| Output Frequency | 50/60 Hz | — |
| Output Wiring / Receptacles | — | Hardwired in/out + 2x L6-20R, 2x L6-30R |
| Step-down Transformers Included | Yes (two 5 kVA, 208/240 V to 120 V) | — |
| Efficiency (On-line Mode) | — | Up to 95% |
| Efficiency (ECO Mode) | — | Up to 98% |
| Output Voltage THD | 2% | — |
| Crest Factor | 3:1 | — |
| Surge Energy Rating | 480 J | — |
| Noise Level | 55 dB | — |
| Management Interfaces | Web-based (details not specified in provided specs) | SNMP/Web (pre-installed RDU120 card), USB, RS485, RS232, terminal block |
| Local Display | — | Full-color graphic LCD with gravity-sensing orientation |
| Certifications | — | ENERGY STAR 2.0, UL1778, c-UL, RoHS2, REACH |
| Web Management | Yes | Yes (SNMP + web, factory pre-installed) |
| Audible Alarm | Yes | — |
| Auto-restart | Yes | — |
| Operating Temperature | — | +32 to +104 °F (0 to +40 °C) |
| Weight | — | 166.4 lbs |
| Dimensions (H x W x D) | — | 8.5 x 16.9 x 24.8 in |
Frequently Asked Questions
Which should you choose: the SRT10KXLT-5KTF2 or the GXT5-10KHVRT5UXLN?
The SRT10KXLT-5KTF2 is the stronger choice when a facility must simultaneously power both 120 V and 208/240 V equipment from a single 10 kVA UPS, because the two bundled step-down transformers are a hardware capability the GXT5-10KHVRT5UXLN does not offer per the supplied specs. The APC unit also accepts a wider input range (100–275 V vs. 176–288 V), providing greater tolerance for unstable utility power. Conversely, the GXT5-10KHVRT5UXLN holds measurable advantages where efficiency and compliance matter: it documents up to 98% ECO-mode / 95% on-line efficiency and carries ENERGY STAR 2.0, UL1778, and RoHS2 listings, none of which appear in the APC spec set provided. The Vertiv also ships with an SNMP/web card pre-installed versus the APC's undetailed management interface. Choose the APC for mixed-voltage rack environments; choose the Vertiv for efficiency-rated, single-voltage 208 V deployments requiring out-of-the-box network management.
Can the SRT10KXLT-5KTF2 or GXT5-10KHVRT5UXLN power standard 120 V North American servers directly?
Based on the provided specs, only the APC SRT10KXLT-5KTF2 explicitly supports 120 V output, enabled by its two bundled 208/240 V to 120 V step-down transformers. The Vertiv GXT5-10KHVRT5UXLN output is configurable only between 200 and 240 VAC per the supplied specifications; 120 V output capability is not listed.
Do I need to buy a separate network management card for either of these UPS units?
The Vertiv GXT5-10KHVRT5UXLN includes a factory pre-installed Liebert IntelliSlot RDU120 SNMP/web card, so no additional purchase is required for SNMP and web management. The APC SRT10KXLT-5KTF2 specifications confirm web-based management is supported, but do not state whether a network management card is pre-installed or sold separately; that detail is absent from the provided spec data.
Which unit is more energy-efficient for a 24/7 data center environment?
The Vertiv GXT5-10KHVRT5UXLN is the only unit with published efficiency figures in the provided specs: up to 98% in Active ECO Mode and up to 95% in on-line double-conversion mode, backed by ENERGY STAR 2.0 certification. No efficiency percentage is listed in the APC SRT10KXLT-5KTF2 specifications provided, so a direct numerical comparison cannot be made from the available data.
More UPS Comparisons
- APC by Schneider Electric SRTL10KRM4UT-5KTF2 vs Panduit U10N32V
- APC by Schneider Electric SRTL10KRM4UT-5KTF2 vs Panduit U10N11V
- APC by Schneider Electric SRTL10KRM4UT-5KTF2 vs Panduit U10N12V
- APC by Schneider Electric SRTL10KRM4UT-5KTF2 vs Vertiv GXT5-10KHVRT5UXLN
- APC by Schneider Electric SRTL10KRM4UT-5KTF2 vs APC by Schneider Electric E3SUPS10KFBS
- APC by Schneider Electric SRTL10KRM4UT-5KTF2 vs APC by Schneider Electric SRT10KRMXLT-10KTF
UPS Buying Guides
Get a Second Opinion on Your Camera Choice
Share your site layout, coverage goals, and budget. Our team will validate the camera selection, flag anything we would change, and recommend products that match the use case.