APC by Schneider Electric BN1350M2 vs Vertiv PSA6-1350LVT

UPS COMPARISON

APC by Schneider Electric BN1350M2 vs Vertiv PSA6-1350LVT: Specification Comparison

Both the APC BN1350M2 and the Vertiv PSA6-1350LVT are 1350VA line-interactive desktop UPS units designed for 120VAC North American environments, making them direct cross-shop candidates for installers and IT buyers protecting workstations, NVRs, access-control servers, and small network closets. This comparison examines runtime and power capacity, physical and connectivity features, and warranty and serviceability — the three axes that most differentiate 1350VA desktop UPS units at the point of purchase.



Which UPS delivers more usable runtime and output capacity for your load?

The APC BN1350M2 is rated at 810 W / 1350 VA with a documented half-load runtime of 10.4 minutes and a full-load runtime of 2.6 minutes. The Vertiv PSA6-1350LVT is rated at 850 W / 1350 VA. The Vertiv carries a 40 W higher watt rating, but no half-load or full-load runtime figures are provided in the supplied specifications for the PSA6-1350LVT, making a direct runtime comparison impossible from available data.

The BN1350M2 uses a lead-acid battery rated at 153 VAh and requires up to 16 hours to fully recharge. Its transfer time is specified at 8–10 ms with a simulated sine wave output. The PSA6-1350LVT provides no published transfer time, waveform type, battery chemistry, capacity, or recharge time in the supplied specifications. Buyers requiring documented runtime curves or sine-wave output should factor in the BN1350M2's published data advantage.


Which unit provides better outlet coverage, surge protection, and line conditioning?

The APC BN1350M2 offers 10 total NEMA 5-15R outlets: 6 with battery backup and surge protection, and 4 with surge protection only, including 2 transformer-spaced outlets. Surge protection is rated at 1,080 joules. It also includes RJ45 data-line protection, coaxial 1-in/1-out protection, 5% noise filtering, and 2 USB charging ports. Input voltage range is 88–139 VAC, providing AVR (Automatic Voltage Regulation) across that window.

The Vertiv PSA6-1350LVT specifications supplied do not enumerate outlet count, outlet configuration, surge joule rating, data-line protection, coaxial protection, USB ports, noise filtering percentage, or input voltage range. The form factor is listed as Desktop/Tower. Installers protecting multi-device security panels or NVR stacks with peripheral cabling should note that the BN1350M2's protection feature set is fully documented while the PSA6-1350LVT's equivalent capabilities cannot be verified from available specifications.


Which UPS offers stronger warranty coverage and easier long-term serviceability?

The Vertiv PSA6-1350LVT carries an explicitly stated 3-year full-unit warranty including battery coverage with advanced replacement — a meaningful differentiator, as most entry UPS warranties exclude batteries or offer only 1–2 years. No equivalent warranty duration or terms are stated in the supplied APC BN1350M2 specifications.

The BN1350M2 does specify a user-replaceable battery (part number APCRBC162), which supports field serviceability without returning the unit. It also lists communications interfaces (USB and serial via RJ45) enabling UPS management software integration. The PSA6-1350LVT supplies no replacement battery part number and no communications interface details in the provided specifications. For managed environments requiring UPS monitoring, the BN1350M2's documented interfaces are an advantage; for warranty-sensitive deployments, the Vertiv's 3-year battery-inclusive coverage is a concrete differentiator.


Which should you choose: the BN1350M2 or the PSA6-1350LVT?

Our take: The BN1350M2 is the stronger choice when documented runtime, outlet count, surge protection detail, and UPS management integration are decision criteria. It provides 10 outlets with 1,080-joule surge protection, a specified 10.4-minute half-load runtime, 8–10 ms transfer time, coaxial and RJ45 data-line protection, and USB/serial management interfaces — all absent or unspecified in the PSA6-1350LVT's available data. The PSA6-1350LVT counters with a 40 W higher watt ceiling (850 W vs 810 W) and a clearly stated 3-year battery-inclusive advanced-replacement warranty, neither of which the BN1350M2 matches based on supplied specs. Choose the BN1350M2 for security-system closets requiring multi-device outlet coverage and verified runtime data. Choose the PSA6-1350LVT where long-term warranty coverage and a slightly higher watt capacity are the primary requirements and the missing specification gaps can be resolved via Vertiv's datasheet.


Side-by-Side Comparison

Spec-for-spec, from manufacturer data.

SpecificationAPC by Schneider Electric BN1350M2Vertiv PSA6-1350LVT
VA Rating1350 VA1350 VA
Watt Rating810 W850 W
UPS TopologyLine InteractiveLine Interactive (implied by sub-brand; not explicitly stated in supplied specs)
Nominal Input Voltage120 VAC120 VAC
Input Voltage Range88–139 VAC
Nominal Output Voltage120 VAC120 VAC
Transfer Time8–10 ms
WaveformSimulated Sine Wave
Total Outlets10x NEMA 5-15R
Battery-Backed Outlets6x NEMA 5-15R
Surge-Only Outlets4x NEMA 5-15R
Surge Protection1,080 Joules
Data Line ProtectionRJ45
Coax Protection1-In / 1-Out
Half-Load Runtime10.4 min
Full-Load Runtime2.6 min
Battery ChemistryLead-Acid
Battery Capacity153 VAh
Recharge Time16 hours
Replacement BatteryAPCRBC162
CommunicationsUSB, Serial via RJ45
USB Charging Ports2
Noise Filtering5%
Noise Level45 dBA
Form FactorDesktop/Tower
Dimensions (W×H×D)3.94 × 10.24 × 14.49 in4.72 × 11.42 × 16.93 in (W×H×D)
Weight29 lb25.8 lb
Warranty3-year full unit incl. battery, advanced replacement
CertificationsENERGY STAR, FCC, NOM, cTUVus
Plug TypeNEMA 5-15P

Frequently Asked Questions

Which should you choose: the BN1350M2 or the PSA6-1350LVT?

The BN1350M2 is the stronger choice when documented runtime, outlet count, surge protection detail, and UPS management integration are decision criteria. It provides 10 outlets with 1,080-joule surge protection, a specified 10.4-minute half-load runtime, 8–10 ms transfer time, coaxial and RJ45 data-line protection, and USB/serial management interfaces — all absent or unspecified in the PSA6-1350LVT's available data. The PSA6-1350LVT counters with a 40 W higher watt ceiling (850 W vs 810 W) and a clearly stated 3-year battery-inclusive advanced-replacement warranty, neither of which the BN1350M2 matches based on supplied specs. Choose the BN1350M2 for security-system closets requiring multi-device outlet coverage and verified runtime data. Choose the PSA6-1350LVT where long-term warranty coverage and a slightly higher watt capacity are the primary requirements and the missing specification gaps can be resolved via Vertiv's datasheet.

Does the BN1350M2 or PSA6-1350LVT include battery warranty coverage?

The Vertiv PSA6-1350LVT explicitly includes battery coverage in its 3-year full-unit warranty with advanced replacement. The APC BN1350M2 specifications supplied do not state a warranty duration or whether the battery is covered. The BN1350M2 does identify a user-replaceable battery (APCRBC162), but warranty terms are not confirmed in the available data.

Can I monitor either UPS remotely or connect it to UPS management software?

The APC BN1350M2 provides USB and serial (via RJ45) communications interfaces, enabling connection to UPS management software such as APC PowerChute. The Vertiv PSA6-1350LVT specifications supplied include no communications interface details, so remote monitoring capability cannot be confirmed from available data.

Which unit protects more devices and peripheral cabling?

The APC BN1350M2 specifies 10 NEMA 5-15R outlets (6 battery-backed, 4 surge-only), plus coaxial 1-in/1-out and RJ45 data-line protection. The Vertiv PSA6-1350LVT specifications supplied do not list outlet count, coaxial protection, or data-line protection, so a direct comparison cannot be made from available data alone.