Vertiv GXT5-5000MVRT4UXLN vs Panduit U05N11V: Specification Comparison
Both the Vertiv GXT5-5000MVRT4UXLN and the Panduit SteadySine U05N11V are 5 kVA online double-conversion UPS units targeting data center, edge, and enterprise rack installations. Buyers evaluating these two will weigh differences in power factor and real wattage, physical form factor and serviceability, and management and integration depth. This comparison draws strictly from the provided specifications for each model and flags gaps where data is absent for one unit.
In This Guide
- How do actual power output, efficiency, and power factor compare between the two units?
- What are the form factor, physical dimensions, and field serviceability differences between the two units?
- How do the management interfaces, protocol support, and certifications differ between the two units?
- Which should you choose: the GXT5-5000MVRT4UXLN or the U05N11V?
- Side-by-Side Specs
- FAQ
How do actual power output, efficiency, and power factor compare between the two units?
The Vertiv GXT5-5000MVRT4UXLN is rated at 5,000 VA and 5,000 W, implying a unity (1.0) power factor. It delivers up to 98% efficiency in Active ECO Mode and up to 95% efficiency in online double-conversion mode. Input voltage is specified at a typical 208 VAC with a range of 176–280 VAC, and output is 208/120 VAC user-configurable.
The Panduit U05N11V is rated at 5 kVA / 4.5 kW, reflecting a 0.9 power factor. This means the Panduit delivers 500 W less usable real power than the Vertiv at the same VA rating. Output waveform is specified as pure sine wave with less than 3% THD. No input voltage range, efficiency rating, or configurable output voltage options are stated in the provided Panduit specifications.
For loads requiring the full 5,000 W of real power, the Vertiv's unity power factor is a meaningful advantage. Buyers whose critical loads add up to 4.5 kW or less will find the Panduit's rated wattage sufficient, but the Vertiv leaves more headroom without derating.
What are the form factor, physical dimensions, and field serviceability differences between the two units?
The Vertiv GXT5-5000MVRT4UXLN occupies 6.8 in (approximately 4U) of rack height, with a width of 16.9 in and a depth of 25.6 in. It weighs 125.6 lb and offers a flexible rack/tower form factor. Wiring is hardwired in and out, with optional Power Distribution (POD) modules available as accessories.
The Panduit U05N11V is a 3U rackmount unit measuring 10.3 in tall (in absolute terms, though specified as 3U rack), 17.3 in wide, and no depth is listed in the provided specifications. It features hot-swappable battery modules and serviceable fan assemblies, which are explicit field-serviceability advantages. No weight is listed for the Panduit.
The Panduit's 3U profile is more rack-space-efficient than the Vertiv's approximately 4U footprint. Hot-swap batteries and fan assemblies on the Panduit allow maintenance without load transfer or downtime. The Vertiv's depth (25.6 in) is documented; Panduit depth is not provided, which may affect shallow-rack or edge-cabinet installations.
How do the management interfaces, protocol support, and certifications differ between the two units?
The Vertiv GXT5-5000MVRT4UXLN ships with a factory pre-installed Vertiv RDU101 SNMP/Webcard, providing SNMP and web management out of the box. Additional interfaces include USB, RS-485, RS-232, a terminal block, and an external battery connector. A full-color graphic LCD with gravity-sensing orientation is included on the control panel. Certifications include ENERGY STAR 2.0, UL 1778, c-UL, RoHS2, and REACH.
The Panduit U05N11V provides a network card slot (card not specified as factory-installed), USB, and serial interfaces. No SNMP card inclusion or web management capability is confirmed as standard in the provided specifications. Certifications listed are UL 1778 and cUL only. No LCD or local display specification is provided.
The Vertiv's factory-installed SNMP/Webcard is a significant operational advantage for IT teams requiring immediate remote monitoring without additional purchases. The Panduit's network card slot indicates expansion capability but requires verification of card availability and cost. The Vertiv also carries a broader certification set, including ENERGY STAR 2.0 and RoHS2/REACH, which are relevant for sustainability compliance requirements.
Which should you choose: the GXT5-5000MVRT4UXLN or the U05N11V?
Our take: The GXT5-5000MVRT4UXLN is the stronger choice when maximum real-power output, out-of-box remote management, and broad compliance certification are the primary requirements. On real wattage, the Vertiv delivers 5,000 W versus the Panduit's 4,500 W — a 500 W (11%) difference driven by the Panduit's 0.9 power factor. The Vertiv also includes a factory-installed SNMP/Webcard for immediate remote monitoring, whereas the Panduit ships with only a network card slot. The Vertiv holds ENERGY STAR 2.0, RoHS2, and REACH certifications not listed for the Panduit. However, the Panduit U05N11V's 3U profile saves approximately 1U of rack space, and its hot-swappable battery modules and fan assemblies offer a documented serviceability advantage not confirmed in the Vertiv's provided specs. Buyers in high-density data centers prioritizing rack efficiency and in-service battery replacement should weigh the Panduit's serviceability features against the Vertiv's power and management advantages.
Side-by-Side Comparison
Spec-for-spec, from manufacturer data.
| Specification | Vertiv GXT5-5000MVRT4UXLN | Panduit U05N11V |
|---|---|---|
| Device Type | Online Double-Conversion UPS | Online Double-Conversion UPS (VFI) |
| Power Rating (VA) | 5,000 VA | 5,000 VA |
| Power Rating (W) | 5,000 W | 4,500 W |
| Power Factor | 1.0 (implied) | 0.9 |
| Form Factor | Rack/Tower (flexible) | 3U Rackmount |
| Height | 6.8 in (~4U) | 10.3 in (3U) |
| Width | 16.9 in | 17.3 in (440 mm) |
| Depth | 25.6 in | — |
| Weight | 125.6 lb | — |
| Efficiency | Up to 98% ECO / 95% online | — |
| Input Voltage Range | 176–280 VAC (typical 208 VAC) | — |
| Output Voltage | 208/120 VAC (user-configurable) | — |
| Output Waveform / THD | — | Pure sine wave, <3% THD |
| Network Management | Factory pre-installed SNMP/Webcard (RDU101) | Network card slot (card not confirmed included) |
| Additional Interfaces | USB, RS-485, RS-232, terminal block, ext. battery connector | USB, serial |
| Hot-Swap Batteries | — | Yes |
| Certifications | ENERGY STAR 2.0, UL 1778, c-UL, RoHS2, REACH | UL 1778, cUL |
| Airflow Pattern | — | Front-to-rear |
| Local Display | Full-color graphic LCD (gravity-sensing) | — |
Frequently Asked Questions
Which should you choose: the GXT5-5000MVRT4UXLN or the U05N11V?
The GXT5-5000MVRT4UXLN is the stronger choice when maximum real-power output, out-of-box remote management, and broad compliance certification are the primary requirements. On real wattage, the Vertiv delivers 5,000 W versus the Panduit's 4,500 W — a 500 W (11%) difference driven by the Panduit's 0.9 power factor. The Vertiv also includes a factory-installed SNMP/Webcard for immediate remote monitoring, whereas the Panduit ships with only a network card slot. The Vertiv holds ENERGY STAR 2.0, RoHS2, and REACH certifications not listed for the Panduit. However, the Panduit U05N11V's 3U profile saves approximately 1U of rack space, and its hot-swappable battery modules and fan assemblies offer a documented serviceability advantage not confirmed in the Vertiv's provided specs. Buyers in high-density data centers prioritizing rack efficiency and in-service battery replacement should weigh the Panduit's serviceability features against the Vertiv's power and management advantages.
Does either UPS include a network management card in the box, or do I have to buy one separately?
The Vertiv GXT5-5000MVRT4UXLN includes a factory pre-installed Vertiv RDU101 SNMP/Webcard as standard, enabling SNMP and web management immediately on installation. The Panduit U05N11V has a network card slot but the provided specifications do not confirm a card is included; assume it requires a separate purchase and verify with Panduit before ordering.
Which unit is better for a shallow or space-constrained rack environment?
The Panduit U05N11V is specified as 3U, saving approximately 1U of rack space compared to the Vertiv's 6.8 in (approximately 4U) height. However, no depth specification is provided for the Panduit, so buyers with shallow racks should obtain that dimension from Panduit before purchasing. The Vertiv's depth is documented at 25.6 in.
Can batteries be replaced in the field without taking the UPS offline?
The Panduit U05N11V explicitly specifies hot-swappable battery modules and serviceable fan assemblies, enabling in-service maintenance. The Vertiv GXT5-5000MVRT4UXLN's provided specifications do not address hot-swap battery capability, so buyers with runtime or serviceability requirements should confirm this with Vertiv before specifying the unit.
More UPS Comparisons
- APC by Schneider Electric SRTL5KRM2UT-5KRMTF vs Panduit U05N11V
- APC by Schneider Electric SRTL5KRM2UT-5KRMTF vs Vertiv GXT5-5000HVRT5UXLN
- APC by Schneider Electric SRTL5KRM2UT-5KRMTF vs Vertiv GXT5-5000MVRT4UXLN
- APC by Schneider Electric SRTL5KRM2UT-5KRMTF vs APC by Schneider Electric SRTL5KRMTF
- APC by Schneider Electric SRT5KRMTF vs Vertiv GXT5-5000HVRT5UXLN
- APC by Schneider Electric SRT5KRMTF vs Vertiv GXT5-5000MVRT4UXLN
UPS Buying Guides
Get a Second Opinion on Your Camera Choice
Share your site layout, coverage goals, and budget. Our team will validate the camera selection, flag anything we would change, and recommend products that match the use case.