APC by Schneider Electric SRT5KRMXLIM vs Vertiv GXT5LI-5000MVRT3UXLN

UPS COMPARISON

APC by Schneider Electric SRT5KRMXLIM vs Vertiv GXT5LI-5000MVRT3UXLN: Specification Comparison

Both the APC Smart-UPS SRT 5000VA RM 230V Marine (SRT5KRMXLIM) and the Vertiv GXT5 LI 5000VA 208/120V RT XL (GXT5LI-5000MVRT3UXLN) are 5000VA rack-mount, double-conversion online UPS units aimed at critical infrastructure protection in data centers, server rooms, and industrial environments. Buyers evaluating this class typically weigh power efficiency, battery technology, voltage and frequency compatibility, physical footprint, and management interface options. This comparison draws exclusively from the provided specifications for each unit.



How do the SRT5KRMXLIM and GXT5LI-5000MVRT3UXLN differ in power output, voltage compatibility, and waveform quality?

The SRT5KRMXLIM is rated at 5000VA / 4500W, giving it a 0.9 power factor, and operates on a 230V output rail (220–230V range) with a 160–275V input acceptance window and 45–65 Hz input frequency tolerance — attributes well-suited to European and marine single-phase 230V environments. Output THD is specified at 3% under load, and the crest factor is rated 3:1, indicating the inverter can handle non-linear loads such as switching power supplies without clipping.

The GXT5LI-5000MVRT3UXLN is rated at 5000VA / 5000W, yielding a unity (1.0) power factor — a meaningful advantage for loads that draw close to rated wattage. It supports 120V/208V output (user-configurable to 120V/240V) and accepts 120V/240V input via a NEMA L14-30P hardwire connection, making it a North American market unit. Output THD, crest factor, and input frequency range are not stated in the provided specifications.

For buyers on 230V single-phase infrastructure (including marine installations), the SRT5KRMXLIM is the only spec-confirmed option here. For North American 208V or 120/240V split-phase environments, the GXT5LI-5000MVRT3UXLN is the applicable unit. The 500W difference in real-power output (4500W vs 5000W) is material when sizing for high-density loads.


What does each unit offer in terms of battery technology, runtime scalability, and energy storage design?

The GXT5LI-5000MVRT3UXLN is explicitly a lithium-ion (Li-Ion) UPS, as evidenced by its UL 1642 (Li-Ion Battery Cells) and UL 1973 (Li-Ion Battery Pack w/UPS) safety listings. Li-Ion chemistry typically delivers longer calendar life (often 8–10 years vs 3–5 for VRLA), faster recharge times, lighter weight per kWh, and a wider operating temperature tolerance before derating. The model name suffix 'XL' and 'RT' suggest extended runtime and rack/tower form factor capability, though specific runtime curves and external battery module compatibility are not included in the provided specs.

The SRT5KRMXLIM specifications do not state battery chemistry. The 'SRT' APC platform is known in the market for supporting both internal and external battery modules, and the 'XLIM' suffix is consistent with APC's extended-runtime marine variants, but neither battery type nor runtime figures appear in the provided specification data and therefore cannot be claimed here.

Buyers with a strong preference for Li-Ion longevity and reduced weight — common in marine, edge, or space-constrained deployments — can confirm that chemistry only for the GXT5LI-5000MVRT3UXLN from the provided specs. Battery runtime figures are absent for both models and should be obtained from each manufacturer's runtime curves before finalizing a selection.


How do the two units compare on monitoring interfaces, certifications, and environmental operating range?

The GXT5LI-5000MVRT3UXLN lists its interface options explicitly: Serial Port, Network RJ-45 (RDU101 network management card), and USB. It carries a comprehensive certification stack: UL 1778, c-UL, CSA 22.2 No. 107.3, FCC Part 15 Class A, Energy Star 2.0, plus the Li-Ion-specific UL 1642 and UL 1973. Operating temperature is specified as 32°F–104°F (0°C–40°C) with a 10% derating noted at 50°C. Physical dimensions are provided: 5.2 in H × 16.9 in W × 35 in D, 104.9 lbs.

The SRT5KRMXLIM specifications confirm Emergency Power Off (EPO) support, audible alarms, temperature-based voltage compensation, and a surge energy rating of 480 J with surge protection. Management interface types (network card, USB, serial) are not listed in the provided specs. Certifications, operating temperature range, and physical dimensions are also absent from the provided data.

For IT buyers who require documented network management capability, energy efficiency certification (Energy Star 2.0), or need to verify rack unit space before procurement, the GXT5LI-5000MVRT3UXLN provides those answers directly from the provided specs. The SRT5KRMXLIM's EPO and temperature voltage compensation are confirmed features not listed for the Vertiv unit, but full management and physical data for the APC unit would need to be sourced from APC's published datasheet.


Which should you choose: the SRT5KRMXLIM or the GXT5LI-5000MVRT3UXLN?

Our take: The GXT5LI-5000MVRT3UXLN is the stronger choice when the deployment is on North American 208V or 120/240V infrastructure and Li-Ion battery longevity, unity power factor, and documented network management are priorities. It delivers 5000W real power versus the SRT5KRMXLIM's 4500W — a 500W (11%) advantage that matters in high-density racks — and its confirmed Li-Ion chemistry (UL 1973 listed) provides longer expected battery service life than conventional VRLA. Its RJ-45 network management port, Energy Star 2.0 rating, and full UL/CSA/FCC certification stack are all spec-confirmed. Conversely, the SRT5KRMXLIM is the applicable unit for 230V single-phase or marine environments (160–275V input window, 45–65 Hz tolerance, EPO, temperature voltage compensation) where the GXT5LI-5000MVRT3UXLN's North American voltage/wiring spec does not apply. Buyers should obtain runtime curves and physical dimensions for the SRT5KRMXLIM from APC's datasheet before finalizing, as those specs were not present in the data provided.


Side-by-Side Comparison

Spec-for-spec, from manufacturer data.

SpecificationAPC by Schneider Electric SRT5KRMXLIMVertiv GXT5LI-5000MVRT3UXLN
TopologyDouble-Conversion OnlineDouble-Conversion Online
VA Rating5000 VA5000 VA
Real Power Output4500 W5000 W
Power Factor0.901.00
Input Voltage Range160–275 V120V / 240V
Input Wiring / ConnectorNEMA L14-30P
Output Voltage Range220–230 V120V/208V (configurable 120V/240V)
Input Frequency45–65 Hz
Output Frequency50/60 Hz
WaveformPure Sine
Output THD3%
Crest Factor3:1
Battery ChemistryLithium-Ion (UL 1642 / UL 1973)
Surge Energy Rating480 J
Emergency Power Off (EPO)Yes
Management InterfacesSerial, RJ-45 (RDU101), USB
Operating Temperature0°C–40°C (derate at 50°C)
CertificationsUL 1778, c-UL, CSA 22.2 No. 107.3, FCC Part 15 Class A, Energy Star 2.0, UL 1642, UL 1973
Noise Level55 dB
Dimensions (H × W × D)5.2 in × 16.9 in × 35 in
Weight104.9 lbs
Audible AlarmsYes
Temperature Voltage CompensationYes

Frequently Asked Questions

Which should you choose: the SRT5KRMXLIM or the GXT5LI-5000MVRT3UXLN?

The GXT5LI-5000MVRT3UXLN is the stronger choice when the deployment is on North American 208V or 120/240V infrastructure and Li-Ion battery longevity, unity power factor, and documented network management are priorities. It delivers 5000W real power versus the SRT5KRMXLIM's 4500W — a 500W (11%) advantage that matters in high-density racks — and its confirmed Li-Ion chemistry (UL 1973 listed) provides longer expected battery service life than conventional VRLA. Its RJ-45 network management port, Energy Star 2.0 rating, and full UL/CSA/FCC certification stack are all spec-confirmed. Conversely, the SRT5KRMXLIM is the applicable unit for 230V single-phase or marine environments (160–275V input window, 45–65 Hz tolerance, EPO, temperature voltage compensation) where the GXT5LI-5000MVRT3UXLN's North American voltage/wiring spec does not apply. Buyers should obtain runtime curves and physical dimensions for the SRT5KRMXLIM from APC's datasheet before finalizing, as those specs were not present in the data provided.

Which UPS — the SRT5KRMXLIM or GXT5LI-5000MVRT3UXLN — is suitable for a marine or international 230V installation?

Based on the provided specifications, only the SRT5KRMXLIM is confirmed for 230V single-phase use, with an input voltage window of 160–275V and a 45–65 Hz frequency tolerance explicitly noted. The GXT5LI-5000MVRT3UXLN is specified for 120V/240V North American input via a NEMA L14-30P connector and is not spec-confirmed for 230V marine or international deployments.

Does either the SRT5KRMXLIM or GXT5LI-5000MVRT3UXLN use lithium-ion batteries, and why does that matter?

The GXT5LI-5000MVRT3UXLN is confirmed as a lithium-ion UPS by its UL 1642 and UL 1973 safety listings in the provided specifications. Li-Ion chemistry typically offers longer calendar life (often 8–10 years vs 3–5 for VRLA), faster recharge, and lighter weight — advantages relevant to edge, medical, and space-constrained deployments. The SRT5KRMXLIM's battery chemistry is not stated in the provided specifications and cannot be confirmed from the data available.

Which unit provides better support for IT network management and remote monitoring?

The GXT5LI-5000MVRT3UXLN lists Serial Port, Network RJ-45 (RDU101), and USB interfaces in its provided specifications, giving installers a confirmed path to network-based monitoring. The SRT5KRMXLIM's provided specifications do not list management interface types; buyers should consult APC's published datasheet to confirm network management card availability before selecting it for a managed infrastructure deployment.