APC by Schneider Electric SRT8KXLT-IEC vs Vertiv GXT5LI-8000MVRT4UXLN: Specification Comparison
Both units are 8000VA double-conversion online UPS systems designed for demanding IT and data-center environments, making them direct cross-shop candidates. The APC Smart-UPS SRT8KXLT-IEC and the Vertiv GXT5 LI GXT5LI-8000MVRT4UXLN share the same VA and watt rating, the same online double-conversion topology, and target rackmount infrastructure loads. This comparison examines power quality and efficiency, physical installation and environmental envelope, and connectivity and compliance — the three axes most relevant to an installer or IT buyer evaluating 8kVA online UPS platforms.
In This Guide
- Which unit delivers better power quality and efficiency under load?
- How do the two units compare for physical installation and operating environment?
- Which unit offers more connectivity options and carries stronger compliance certifications?
- Which should you choose: the SRT8KXLT-IEC or the GXT5LI-8000MVRT4UXLN?
- Side-by-Side Specs
- FAQ
Which unit delivers better power quality and efficiency under load?
The SRT8KXLT-IEC specifies an efficiency of 98.5% at double-conversion operation, output voltage THD of 2%, and a crest factor of 3:1 — all published figures that directly affect heat dissipation, runtime, and downstream equipment compatibility. Its sine-wave output, AVR, and 480 J surge energy rating round out the power-quality picture. The unit also lists a 55 dB acoustic noise level.
The GXT5LI-8000MVRT4UXLN is rated at 8000VA / 8000W, giving it a unity power factor — meaning its watt output equals its VA rating. No efficiency percentage, output THD, crest factor, surge joule rating, or acoustic noise figure is provided in the available specifications. The unity power factor (8000 W from 8000 VA) is a notable differentiator, whereas the SRT8KXLT-IEC's watt rating equals its VA rating as well (8000 W / 8 kVA), so both units share a unity power factor by the numbers provided.
On the specs at hand, the SRT8KXLT-IEC provides substantially more granularity — 98.5% efficiency, 2% output THD, 3:1 crest factor, and a joule surge rating — giving specifiers a concrete basis for energy cost and equipment-protection calculations. None of those figures are available for the GXT5LI-8000MVRT4UXLN from the supplied data.
How do the two units compare for physical installation and operating environment?
The GXT5LI-8000MVRT4UXLN has fully documented physical dimensions: 6.9 in H × 16.9 in W × 35 in D, weighing 156.3 lbs. Its operating temperature range is 32°F to 104°F (0°C to 40°C) with a 10% derating noted at 50°C. Wiring is hardwired (L1, L2, N, G), which is important for facilities planning and NEC compliance. Battery chemistry is lithium-ion, as indicated by its UL 1642 and UL 1973 listings.
The SRT8KXLT-IEC does not provide physical dimensions or weight in the supplied specifications, nor is an operating temperature range listed. Its IEC designation and output voltage range of 208–240 V indicate a focus on IEC-outlet-equipped international or data-center deployments. Input voltage acceptance spans 100–275 V with a frequency window of 40–70 Hz, indicating broad input tolerance. No battery chemistry is specified in the available data.
Installers needing to validate rack space, floor loading, or thermal headroom have complete data for the GXT5LI-8000MVRT4UXLN and incomplete data for the SRT8KXLT-IEC from the specs provided. The Vertiv's hardwired connection method also has direct implications for electrical rough-in planning that the APC unit's spec sheet does not address in the available data.
Which unit offers more connectivity options and carries stronger compliance certifications?
The GXT5LI-8000MVRT4UXLN lists three interface options: Serial Port, Network RJ-45 (via RDU101 card), and USB. Its compliance portfolio is detailed: UL 1642, UL 1973, UL 1778, CSA 22.2 No. 107.3, c-UL, FCC Part 15 Class A, and Energy Star 2.0. The Energy Star 2.0 designation is relevant for organizations with sustainability mandates or rebate programs.
The SRT8KXLT-IEC specifies Emergency Power Off (EPO) support — a critical feature for data-center safety and NEC 645.11 compliance — and surge protection. No communication port types (serial, USB, network card) are enumerated in the provided specifications, and no compliance certifications or listings are cited in the available data.
For connectivity and third-party network management integration, the GXT5LI-8000MVRT4UXLN has a documented interface set. For facilities requiring EPO, the SRT8KXLT-IEC explicitly confirms that capability while the GXT5LI-8000MVRT4UXLN does not address EPO in the available specifications. Buyers should verify both omissions — APC's port types and Vertiv's EPO — directly with the respective manufacturers before finalizing a selection.
Which should you choose: the SRT8KXLT-IEC or the GXT5LI-8000MVRT4UXLN?
Our take: The SRT8KXLT-IEC is the stronger choice when power-quality documentation and broad input tolerance are the primary selection criteria. It specifies 98.5% efficiency, 2% output THD, a 3:1 crest factor, and a 100–275 V input range — figures the GXT5LI-8000MVRT4UXLN does not provide in the available data. It also explicitly confirms EPO support. Conversely, the GXT5LI-8000MVRT4UXLN is the better-documented unit for physical installation: full dimensions (6.9 in × 16.9 in × 35 in, 156.3 lbs), hardwired termination details, a defined operating temperature range (0°C–40°C), lithium-ion battery chemistry confirmed by UL 1642/1973 listings, and Energy Star 2.0 certification. Choose the APC for environments demanding proven power-quality specs and wide input voltage swing; choose the Vertiv where rack-layout verification, Li-Ion battery compliance, and Energy Star reporting are non-negotiable requirements.
Side-by-Side Comparison
Spec-for-spec, from manufacturer data.
| Specification | APC by Schneider Electric SRT8KXLT-IEC | Vertiv GXT5LI-8000MVRT4UXLN |
|---|---|---|
| Topology | Double-Conversion Online | Double-Conversion Online |
| Power Rating (VA) | 8000 VA | 8000 VA |
| Power Rating (W) | 8000 W | 8000 W |
| Efficiency | 98.5% | — |
| Output Voltage THD | 2% | — |
| Crest Factor | 3:1 | — |
| Waveform | Sine | — |
| Input Voltage Range | 100–275 V | 120V/240V |
| Input Frequency Range | 40–70 Hz | — |
| Output Voltage Range | 208–240 V | 120V/208V (or 120V/240V, user-configurable) |
| Output Frequency | 50/60 Hz | — |
| Surge Energy Rating | 480 J | — |
| AVR | Yes | — |
| Emergency Power Off (EPO) | Yes | — |
| Wiring / Connection | — | Hardwired (L1, L2, N, G) |
| Communication Interfaces | — | Serial Port, Network RJ-45 (RDU101), USB |
| Battery Chemistry | — | Lithium-Ion (per UL 1642/1973) |
| Operating Temperature | — | 0°C to 40°C (10% derating at 50°C) |
| Noise Level | 55 dB | — |
| Dimensions (H × W × D) | — | 6.9 in × 16.9 in × 35 in |
| Weight | — | 156.3 lbs |
| Energy Star | — | Energy Star 2.0 |
| Safety / EMC Listings | — | UL 1642, UL 1973, UL 1778, CSA 22.2 No. 107.3, c-UL, FCC Part 15 Class A |
Frequently Asked Questions
Which should you choose: the SRT8KXLT-IEC or the GXT5LI-8000MVRT4UXLN?
The SRT8KXLT-IEC is the stronger choice when power-quality documentation and broad input tolerance are the primary selection criteria. It specifies 98.5% efficiency, 2% output THD, a 3:1 crest factor, and a 100–275 V input range — figures the GXT5LI-8000MVRT4UXLN does not provide in the available data. It also explicitly confirms EPO support. Conversely, the GXT5LI-8000MVRT4UXLN is the better-documented unit for physical installation: full dimensions (6.9 in × 16.9 in × 35 in, 156.3 lbs), hardwired termination details, a defined operating temperature range (0°C–40°C), lithium-ion battery chemistry confirmed by UL 1642/1973 listings, and Energy Star 2.0 certification. Choose the APC for environments demanding proven power-quality specs and wide input voltage swing; choose the Vertiv where rack-layout verification, Li-Ion battery compliance, and Energy Star reporting are non-negotiable requirements.
Is the SRT8KXLT-IEC or the GXT5LI-8000MVRT4UXLN more efficient?
The SRT8KXLT-IEC publishes an efficiency rating of 98.5% in double-conversion mode. The GXT5LI-8000MVRT4UXLN does not include an efficiency percentage in the available specifications, so a direct numerical comparison cannot be made from the data provided.
Which unit is easier to plan into a rack or raised-floor environment?
The GXT5LI-8000MVRT4UXLN has documented physical dimensions (6.9 in H × 16.9 in W × 35 in D) and a published weight of 156.3 lbs, enabling precise rack-space and floor-load calculations. The SRT8KXLT-IEC does not provide dimensions or weight in the available specifications, so installers would need to obtain that data from APC directly before completing rack layout.
Does either unit support remote network management out of the box?
The GXT5LI-8000MVRT4UXLN lists Serial Port, Network RJ-45 (via RDU101), and USB interfaces. The SRT8KXLT-IEC does not enumerate communication port types in the available specifications. Buyers requiring network management should confirm port availability and compatible management cards with APC before purchasing the SRT8KXLT-IEC.
More UPS Comparisons
- APC by Schneider Electric SRT8KXLT30 vs Vertiv GXT5LI-8000MVRT4UXLN
- APC by Schneider Electric SRT8KXLT30 vs Vertiv GXT5LI-8000GVRT3UXLN
- APC by Schneider Electric SRT8KXLT30 vs APC by Schneider Electric SRT8KRMXLT-IEC
- APC by Schneider Electric DLRT8KRMXLT vs Vertiv GXT5LI-8000MVRT4UXLN
- APC by Schneider Electric DLRT8KRMXLT vs Vertiv GXT5LI-8000GVRT3UXLN
- APC by Schneider Electric DLRT8KRMXLT vs APC by Schneider Electric SRT8KRMXLT-IEC
UPS Buying Guides
Get a Second Opinion on Your Camera Choice
Share your site layout, coverage goals, and budget. Our team will validate the camera selection, flag anything we would change, and recommend products that match the use case.