APC by Schneider Electric Reliable Rack Power Distribution Designed to Increase - AP6020A

APC by Schneider Electric AP6020A Basic Rack PDU — 20A, 13-Outlet, 0U/1UOverviewThe AP6020A is a single-phase, basic rack rack power distribution unit…

$176.00 $117.99 SAVE $58
Ships same business day
In stock

Quantity:

Adding to cart… The item has been added
Compatibility guidance available for your deployment
Senior specialists for pre and post-sales support
Authorized sourcing and documentation support
Shipping and lead-time confirmation before install

Laura Bennett, IPSD Senior Specialist

Talk to Laura

200+ hrs training • U.S - based

Senior Specialist • 877-277-7147

APC by Schneider Electric Reliable Rack Power Distribution Designed to Increase - AP6020A

$176.00
$117.99

Overview

SKU: AP6020A
UPC: 731304327806
Condition: New

No Bots, Just Experts

Questions about this product? Free pre-sales support from a senior specialist — product questions, compatibility checks, BOM quotes, price confirmation — typically answered within one business day. Need camera placement or system design work? Engineering time is $175 per hour (qty 1 = 1 hour). Hardware buyers get up to one hour ($175) credited back on their order.

Description

APC by Schneider Electric AP6020A Basic Rack PDU — 20A, 13-Outlet, 0U/1U

Overview

The AP6020A is a single-phase, basic rack rack power distribution unit from APC by Schneider Electric built for straightforward, reliable power distribution in server rooms, network closets, and equipment racks where metered or switched complexity isn't needed. It delivers up to 20A of input capacity through a C20 plug, distributing power across 13 IEC 320 C13 outlets — enough to feed a fully populated 1U server shelf or a mixed row of network gear and patch panels without a secondary PDU. The AP6020A accepts 100–240V input at 50–60 Hz, making it usable in both North American and international deployments without swapping hardware.

Key Features

  • 13 IEC 320 C13 Outlets: A full bank of C13 receptacles means standard server, switch, and appliance power cords plug in directly — no adapters, no pigtail chains. Thirteen positions cover a typical 1U or 2U shelf's full load without daisy-chaining a second PDU and adding failure points.
  • 20A C20 Input Plug: The C20 coupler input connects to matching C19/C20 outlets on UPS units or in-row power strips, keeping the power chain all-IEC and compatible with most data-center-grade UPS output panels. The 20A rating gives you headroom above the 16A maximum per-phase draw the unit will actually see in service.
  • 3,680 VA / 3,680W Load Capacity: At full 16A per-phase draw across 100–240V, the AP6020A supports up to 3,680 VA of connected load — roughly equivalent to powering a dense 1U dual-socket server plus its ancillary networking gear simultaneously. Size your connected load to 80% of this ceiling (≈2,944 VA) for safe continuous operation.
  • 0U or 1U Mounting — Horizontal or Vertical: The dual-orientation design means you can run it vertically in the side channel of an open-frame rack (preserving rack-unit real estate) or mount it horizontally in a 1U slot when vertical space in the cabinet is available. Most basic PDUs lock you into one orientation; this one doesn't.
  • 100–240V, 50–60 Hz Universal Input: Wide input voltage tolerance eliminates the need for region-specific SKUs. Deploy the same AP6020A hardware in a US data center at 120V or a European co-location at 230V — no hardware change, no special ordering.
  • 16A Maximum Per-Phase Current: The 16A per-phase ceiling (vs. the 20A input rating) aligns with IEC and NEC best-practice derating. This means you're not bumping against the breaker in normal operation; the 4A headroom absorbs transient inrush from server power supplies without tripping the upstream circuit.
  • RoHS Compliant, Multi-Region Certified: Certifications include cUL Listed, UL Listed, CE, VDE, EAC, IRAM, PSE, and REACH — plus RoHS compliance. That combination clears import and facility requirements across North America, Europe, Japan, Russia, and South America without separate compliance review per region.

Integration and Compatibility

The AP6020A is a passive basic PDU — it distributes power without metering, switching, or network management. This keeps integration simple: it draws from any C20-output UPS or in-row power strip and feeds standard C13 equipment. Because there is no network interface, it requires no IP address, no firmware updates, and no VMS or DCIM integration. Pair it with a UPS with C19/C20 output to maintain runtime during outages, or use it downstream of an in-row transfer switch for redundant-feed architectures.

For deployments where you need real-time current monitoring per outlet or remote switching capability, consider a metered or switched PDU variant within the APC rack PDU family — the AP6020A's basic tier is the right choice when simplicity, cost efficiency, and broad certification coverage matter more than remote visibility. Consult a rack power planning guide to verify load balance across phases before commissioning in high-density rows.

Frequently Asked Questions

Q: What input plug does the AP6020A use, and what does that mean for UPS compatibility?

A: The AP6020A uses a C20 coupler input. Most rack-mount UPS units and in-row power strips with C19 output receptacles are directly compatible — no adapter needed. Verify your upstream UPS output is C19 before ordering.

Q: Can the AP6020A be mounted both horizontally and vertically?

A: Yes. It supports both 0U vertical mounting (in the side channel of open-frame racks, preserving rack-unit space) and 1U horizontal mounting. The choice depends on your cabinet layout and available real estate.

Q: What is the maximum load the AP6020A can support?

A: The unit is rated for 3,680 VA / 3,680W at up to 16A per phase. Best practice is to load it to no more than 80% of capacity (approximately 2,944 VA) for reliable continuous operation and to absorb inrush transients.

Q: Is the AP6020A compatible with international deployments?

A: Yes. It accepts 100–240V input at 50–60 Hz, covering both North American and international voltage standards. It also carries CE, VDE, EAC, IRAM, and PSE certifications alongside North American cUL and UL listings, making it deployable across multiple regions without a hardware swap.

Q: Does the AP6020A have network management or outlet-level monitoring?

A: No. The AP6020A is a basic (non-metered, non-switched) PDU. It has no network interface, no outlet-level monitoring, and no remote switching. If you need per-outlet current data or remote load management, you'll need a metered or switched PDU from APC's rack PDU lineup.

Q: What certifications does the AP6020A carry?

A: cUL Listed, UL Listed, CE, VDE, EAC, IRAM, PSE, and REACH, plus RoHS compliance. This combination satisfies facility and import requirements across North America, Europe, Japan, Russia, and South America.

Marty Allison
Marty Allison

The AP6020A is the PDU I reach for when a rack needs reliable, no-frills power distribution and the project budget doesn't justify paying for metering or switching that nobody in operations will ever log into. The 20A C20 input with a 16A per-phase ceiling gives you a real-world usable capacity of about 2,944 VA when derated properly — that's enough to feed a mixed shelf of 1U servers and access-layer switches without a second PDU eating another rack unit.

Technical Highlights:

  • 13 C13 Outlets: Covers a full shelf of standard gear — servers, switches, patch-panel power injectors — without daisy-chaining. Thirteen positions is the practical maximum before you're looking at a second PDU or a higher-density strip.
  • 3,680 VA Load Capacity: At 80% continuous derating that's 2,944 VA — enough for a dense 1U dual-socket server plus ancillary gear. Don't load it to the 3,680 VA nameplate on a 24/7 circuit.
  • Multi-Region Certification Stack: cUL, UL, CE, VDE, EAC, IRAM, PSE, and REACH in a single SKU means one purchase order covers a North American rollout and a European co-location expansion without re-qualifying hardware.

Deployment Considerations:

  • Confirm your upstream UPS or in-row strip has C19 output before racking the AP6020A — the C20 input is standard but not universal on older UPS models.
  • This is a basic PDU with zero network visibility. If your NOC needs per-outlet current data or remote reboot capability, this is the wrong tier — move up to a metered or switched APC rack PDU variant.

The AP6020A fits cleanly in network closets and secondary equipment rows where the primary goal is outlet density and multi-region compliance, not remote power management — a co-location expansion row or a branch-office IDF cabinet is exactly where this unit earns its keep.

Specifications
PDU types: Basic
Type: Single-phase
Rack capacity: 0U/1U
Mounting: Horizontal/Vertical
Product colour: Black
AC outlets quantity: 13 AC outlet(s)
Power plug: C20 coupler
AC outlet types: C13 coupler
Output connections: IEC 320 C13
Nominal input voltage: 100-240 V
AC input frequency: 50 - 60 Hz
Maximum current: 20 A
Load capacity: 3680 VA
Maximum input current per phase: 16 A
Maximum total current draw per phase: 16 A
Maximum power: 3680 W
Compliance certificates: RoHS
Certification: cUL Listed, CE, EAC, IRAM, PSE, UL Listed, VDE, REACH
Q&A
Reviews
Have Questions?

RELATED PRODUCTS

System Design, Deployment & Technical Support

Support services and planning resources for commercial surveillance, access control, and infrastructure deployments.

Fixed scope • Fixed price

System Design Assistance

  • Get help validating product compatibility
  • Coverage requirements
  • Storage planning and deployment architecture before you buy.
Request Design Help

Deployment & Configuration Support

  • Access fixed-scope support for rollout planning
  • User setup guidance
  • Migration and system standardization across single-site or multi-site deployments
View Support Services

Guides, Tools & Calculators

  • PoE requirements
  • Storage retention
  • Camera selection and deployment methodology
Open Technical Resources