Vertiv BRF060-1023 Basic Nonsurge 20A - 27853
Basic, nonsurge power distribution unit (PDU) designed for rack-mounted IT equipment
Manufacturer-verified compatible cameras, recorders, mounts, accessories, and licenses for this product. Adjust quantities and add the entire bundle to your cart in one click.
Questions about this product? Free pre-sales support from a senior specialist — product questions, compatibility checks, BOM quotes, price confirmation — typically answered within one business day. Need camera placement or system design work? Engineering time is $175 per hour (qty 1 = 1 hour). Hardware buyers get up to one hour ($175) credited back on their order.
The Vertiv 11108 — model VHVRC120-102D20TL6 — is a 1U horizontal rack PDU built for 208V data center and server room environments where you need real-time power visibility without deploying a full network-managed unit. It delivers 20A at 208V (3.3kW load capacity) across 12 NEMA 6-20R receptacles, and every unit ships 100% factory-tested before leaving the line. If you're loading high-density servers, networking gear, or KVM switches into a standard 19-inch rack and you want instant overload awareness at the unit — not via a management console — this is the class of PDU to reach for.
The 11108 is a metered standard unit — meaning it reads aggregate power at the unit level only, not per-outlet. If your environment requires per-outlet switching or per-outlet metering (useful for billing or granular load balancing), step up to a switched or outlet-metered Vertiv rPDU in the same PowerIT line. For environments where the aggregate view is sufficient — most single-tenant server rooms, remote offices with small cabs, and colocation cages where you own the whole PDU — the 11108 delivers the monitoring you need without paying for outlet-level intelligence you won't use.
The L6-20P input plug is compatible with standard 20A 208V circuit breakers found in most North American data center panel boards. Pair this with a rack enclosure rated for the PDU's 17-inch width and confirm your facility's circuit capacity before deploying — 3.3kW continuous at 80% NEC loading means your circuit breaker should be rated for at least 20A, which this PDU's input plug already matches.
For larger deployments requiring centralized monitoring, this unit can coexist in a rack alongside network-managed PDUs without conflict — it simply won't appear on your DCIM dashboard. If remote monitoring of individual rack power distribution circuits becomes a requirement post-deployment, swap to a networked variant in the Vertiv PowerIT family rather than retrofitting.
Q: What is the maximum load capacity of the Vertiv 11108?
A: The 11108 supports a maximum load of 3.3kW at 208V with a 20A input current. All 12 NEMA 6-20R receptacles share a single 20A double pole magnetic breaker, so total connected load across all outlets must not exceed 20A (NEC 80% continuous load rule recommends staying under 16A continuous).
Q: Does the 11108 provide per-outlet metering or switching?
A: No. The 11108 is an aggregate-level metered unit — it monitors total amps, volts, watts, and power factor for the entire PDU via the local LED display. It does not offer per-outlet metering or remote outlet switching. If per-outlet visibility or control is required, a switched or outlet-metered Vertiv rPDU is the appropriate choice.
Q: Is the Vertiv 11108 TAA compliant?
A: Yes. The 11108 is TAA (Trade Agreements Act) compliant and Buy American Act COTS compliant, manufactured in the USA. This makes it eligible for federal, DoD, and many state/local government procurement contracts requiring domestic or TAA-approved country of origin.
Q: What warranty is included with the 11108?
A: Vertiv includes a 5-year limited warranty with the 11108.
Q: What input plug does the 11108 use, and how long is the power cord?
A: The 11108 uses a NEMA L6-20P twistlock plug on a 10-foot, 12/3 AWG power cord. This plug mates with standard 20A 208V twistlock receptacles commonly found in data center power panels and PDPs.
Q: Can the 11108 be monitored remotely over a network?
A: No. The 11108 is a local-display-only metered PDU — power data (A, V, W, PF) is shown on the unit's LED display but is not transmitted over a network. There is no Ethernet port or network management capability on this model. Remote monitoring requires a network-managed Vertiv rPDU variant.

The Vertiv 11108 is one of those PDUs I recommend when teams ask for power visibility without the overhead of network management. The ±2% accuracy on the local RMS meter is the specification I keep coming back to — it's tight enough to use for capacity planning conversations, not just a ballpark check before you plug in the next server. If you're managing a high-density cabinet and you want to know whether you have 3A of headroom before hitting the breaker, that ±2% reading is trustworthy.
Technical Highlights:
Deployment Considerations:
The 11108 is the right fit for government or defense-adjacent data rooms where TAA and Buy American compliance are non-negotiable procurement requirements, and where the operations team wants local power confirmation without adding a managed device to the network inventory. It's particularly well-suited for 4–8 rack deployments in remote or edge facilities where a full DCIM rollout isn't justified but load awareness at the rack still matters.