SKU: SUVTP15KF2B4S
Condition: New
Write a Review 34% OFF

APC by Schneider Electric Smart-ups VT 15KVA 208V W/2 Batt MOD EXP to 4 Start-up - SUVTP15KF2B4S

APC by Schneider Electric SUVTP15KF2B4S Smart-UPS VT 15KVA Rackmount UPS with Internal Maintenance BypassOverviewThe APC by Schneider Electric SUVTP15…

$17,080.00 $11,272.99 SAVE $5807
Ships same business day
In stock

Quantity:

Adding to cart… The item has been added
Compatibility guidance available for your deployment
Senior specialists for pre and post-sales support
Authorized sourcing and documentation support
Shipping and lead-time confirmation before install

Laura Bennett, IPSD Senior Specialist

Talk to Laura

200+ hrs training • U.S - based

Senior Specialist • 877-277-7147

APC by Schneider Electric Smart-ups VT 15KVA 208V W/2 Batt MOD EXP to 4 Start-up - SUVTP15KF2B4S

$17,080.00
$11,272.99

Overview

SKU: SUVTP15KF2B4S
Condition: New

No Bots, Just Experts

Questions about this product? Free pre-sales support from a senior specialist — product questions, compatibility checks, BOM quotes, price confirmation — typically answered within one business day. Need camera placement or system design work? Engineering time is $175 per hour (qty 1 = 1 hour). Hardware buyers get up to one hour ($175) credited back on their order.

Description

APC by Schneider Electric SUVTP15KF2B4S Smart-UPS VT 15KVA Rackmount UPS with Internal Maintenance Bypass

Overview

The APC by Schneider Electric SUVTP15KF2B4S is a 15 kVA / 12,000W three-phase-input rackmount uninterruptible power supply built for data centers, server rooms, and critical infrastructure environments where runtime expandability and zero-downtime serviceability are non-negotiable. It ships with two battery modules and the internal architecture to scale to four — giving you a defined upgrade path without pulling the unit from the rack. The built-in internal maintenance bypass and the 5x8 factory startup service make this a purpose-built choice for environments that can't tolerate planned-maintenance windows any more than unplanned outages.

For integrators specifying power protection for UPS and power protection systems in commercial or enterprise deployments, the SUVTP15KF2B4S sits in the sweet spot between entry-level tower UPS units and full-frame three-phase infrastructure: enough capacity for a dense server rack or mid-size network closet, with the serviceability features that enterprise operations teams actually require.

Key Features

  • 15 kVA / 12,000W Output Capacity: At a 0.8 power factor, this unit delivers 12kW of real power to the load — enough headroom for a fully populated 42U rack of 1U/2U servers or a concentrated switch and storage stack. Size to 80% of rated load maximum; that leaves you at 9.6kW continuous without stressing the UPS or shortening battery life.
  • 93% Operating Efficiency: A 93% efficiency rating means the unit dissipates roughly 840W as heat at full load rather than the 1,200–1,500W you'd see from older transformer-based designs. In a data center environment, every watt of heat you don't generate is a watt your CRAC unit doesn't have to remove — a real operational cost factor at this capacity class.
  • Expandable Battery Architecture (2 Modules, Upgradable to 4): The SUVTP15KF2B4S ships with two sealed lead-acid (VRLA) battery modules installed and the chassis capacity for four. Adding the second pair of modules directly extends runtime without external battery cabinets, rack space reallocation, or additional wiring runs. Runtime planning should be done against your actual load, not rated capacity.
  • 5-Hour Battery Recharge Time: After a full discharge event, VRLA batteries at this capacity class typically need 8–12 hours to recover. The 5-hour recharge spec on this unit means you're back to full protection faster — important in environments with recurring utility instability where back-to-back events are a real risk.
  • Internal Maintenance Bypass: The integrated maintenance bypass lets you isolate the UPS electronics for service or replacement while the connected load stays on utility power — no scheduled outage, no equipment shutdown. For data center power infrastructure where any unplanned downtime carries a cost, this is a practical operational requirement, not an optional upgrade.
  • Emergency Power Off (EPO): The EPO input allows remote emergency shutdown of the UPS output — a code requirement in many data center and raised-floor environments. Verify your local electrical codes for EPO wiring requirements before installation.
  • Low Output Voltage THD (≤5%): Output total harmonic distortion held below 5% means the power delivered to sensitive loads — servers, storage arrays, network switches — is clean enough that equipment power supplies won't add compensating heat or experience premature failure from distorted waveforms. Most enterprise-class equipment is rated for ≤10% THD; this unit gives you a 2× margin.
  • Sealed Lead-Acid (VRLA) Battery Technology: VRLA batteries are maintenance-free in normal operation — no watering, no equalization cycles, no venting requirements that would require a dedicated battery room. They're appropriate for installation in occupied spaces and standard server rooms without special permits in most jurisdictions.
  • Audible Alarm System: Onboard audible alarms provide local notification of on-battery operation, low battery, overload, and fault conditions — a baseline requirement for any unmanned equipment room where staff need immediate physical indication of a power event.
  • Serial Management Port: The single serial port supports direct management connectivity for environments running older DCIM or BMS integrations that rely on RS-232 rather than network-based management cards. If you need SNMP or network management, plan for a separate management card.
  • Wide Environmental Operating Range (0–40°C, 0–95% RH): The operating envelope covers standard data center conditions (18–27°C typical) with significant headroom above and below. The 0–95% non-condensing humidity rating means the unit can tolerate the elevated humidity found in some edge and industrial environments without requiring additional environmental controls.
  • Rackmount Form Factor: Designed for standard 19-inch rack installation, the SUVTP15KF2B4S integrates directly into existing rack infrastructure. Verify rack depth and weight capacity before installation — units at this capacity class are significantly heavier than 1U/2U devices, and the battery modules add substantial additional weight.

Integration & Compatibility

The SUVTP15KF2B4S operates at 208V input, which aligns with standard North American three-phase or split-phase distribution in commercial and data center environments. The single AC outlet configuration is typical for high-capacity UPS units designed to feed a downstream PDU rather than individual devices — factor a compatible rack PDU into your power distribution design. The serial management port covers legacy integration; for modern SNMP-based monitoring through platforms like network management systems or DCIM tools, verify management card availability for this model. The EPO input wiring should be coordinated with your facility's electrical team and reviewed against local code requirements before commissioning. Battery module replacement follows the hot-swap architecture standard to this product line — confirm battery module compatibility at time of purchase if replacements will be sourced separately.

Frequently Asked Questions

Q: What is the actual watt output of the SUVTP15KF2B4S, and how does kVA relate to watts for load planning?

A: The SUVTP15KF2B4S is rated at 15 kVA and 12,000W. The difference reflects a 0.8 power factor. For load planning, use the watt figure (12,000W) as your ceiling — size your connected load to no more than 80% of that, or roughly 9,600W continuous, to preserve battery life and unit longevity.

Q: Can the battery capacity on the SUVTP15KF2B4S be expanded after purchase?

A: Yes. The unit ships with two VRLA battery modules and is designed to accept up to four modules total. Adding the second pair of battery modules directly increases runtime without requiring external battery cabinets or additional rack space beyond the unit's existing footprint.

Q: Does the SUVTP15KF2B4S require a maintenance outage for servicing?

A: No. The integrated internal maintenance bypass allows the UPS electronics to be isolated for service while the connected load continues to receive utility power. This eliminates the need to schedule a service outage for equipment attached to this unit.

Q: What does the 5x8 startup service included with the SUVTP15KF2B4S cover?

A: The 5x8 startup service provides factory-coordinated commissioning support during standard business hours (5 days a week, 8 hours a day). This typically covers initial installation verification and system startup — confirm specific service scope with the service documentation at time of deployment.

Q: What kind of management connectivity does the SUVTP15KF2B4S provide out of the box?

A: Out of the box, the SUVTP15KF2B4S includes one serial (RS-232) port for direct management connectivity. Network-based management (SNMP, web interface) typically requires a separately purchased management card — verify card compatibility for this model before specifying a network-managed deployment.

Q: What input voltage does the SUVTP15KF2B4S require?

A: The SUVTP15KF2B4S is designed for 208V input, standard in North American commercial and data center environments with three-phase or split-phase distribution. Confirm your facility's available voltage before installation — this unit is not designed for 120V single-phase circuits.

James Everett
James Everett

When I spec the SUVTP15KF2B4S for a client, the first number I anchor on is 12,000W at 0.8 PF — not the 15 kVA headline. That watt figure, derated to 9,600W at 80% load ceiling, is what actually drives rack power planning. The 93% efficiency rating is the second number worth internalizing: at full 12kW load you're generating roughly 840W of heat rather than the 1,200–1,500W typical of older transformer-based units at this capacity, which translates directly to reduced cooling load in the room.

Technical Highlights:

  • Internal Maintenance Bypass: Eliminates the need for any planned downtime during UPS service — the connected load stays on utility power while electronics are isolated. At 15 kVA capacity, having this built in rather than bolted on externally simplifies both the initial installation and every future service event.
  • Expandable Battery (2→4 Modules, 5-Hour Recharge): The two-module-to-four upgrade path is a real operational hedge. The 5-hour recharge spec matters most in environments with recurring utility instability — getting back to full runtime protection before the next event is a practical risk factor, not just a spec checkbox.
  • Output THD ≤5%: Holding total harmonic distortion below 5% gives enterprise-class server and storage power supplies twice the margin their ≤10% THD ratings require. In a dense mixed-load rack, clean output waveform reduces compensating heat generation across every connected power supply simultaneously.

Deployment Considerations:

  • The single AC outlet on the SUVTP15KF2B4S means your design must include a downstream rack PDU — this is not a unit you wire individual servers into directly. Factor PDU selection, branch circuit sizing, and outlet count into the complete power distribution design before specifying this unit.
  • Serial management only out of the box is a real constraint for modern environments: if your DCIM or monitoring platform expects SNMP or a network management interface, budget for and verify availability of a compatible network management card before finalizing the BOM.

The SUVTP15KF2B4S is the right call for a mid-density data center row or a consolidated network and storage closet where the operations team needs internal bypass for live serviceability, a defined battery expansion path, and 208V rackmount form factor — particularly in environments where the facility's electrical team has already standardized on APC APC UPS infrastructure for consistency of service and battery replacement logistics.

Specifications
Output power capacity: 15 kVA
Output power: 12000 W
Efficiency: 93%
Emergency Power Off (EPO: Yes
Output voltage Total Harmonic Distortion (THD: 5%
Audible alarm(s: Yes
AC outlets quantity: 1 AC outlet(s)
Serial ports quantity: 1
Battery technology: Sealed Lead Acid (VRLA)
Battery recharge time: 5 h
Form factor: Rackmount
Product colour: Black
Operating temperature (T-T: 0 - 40 °C
Storage temperature (T-T: -50 - 40 °C
Operating relative humidity (H-H: 0 - 95%
Storage relative humidity (H-H: 0 - 95%
Operating altitude: 0 - 999.9 m
Non-operating altitude: 0 - 15000 m
Q&A
Reviews
Have Questions?

RELATED PRODUCTS

System Design, Deployment & Technical Support

Support services and planning resources for commercial surveillance, access control, and infrastructure deployments.

Fixed scope • Fixed price

System Design Assistance

  • Get help validating product compatibility
  • Coverage requirements
  • Storage planning and deployment architecture before you buy.
Request Design Help

Deployment & Configuration Support

  • Access fixed-scope support for rollout planning
  • User setup guidance
  • Migration and system standardization across single-site or multi-site deployments
View Support Services