Questions about this product? Free pre-sales support from a senior specialist — product questions, compatibility checks, BOM quotes, price confirmation — typically answered within one business day. Need camera placement or system design work? Engineering time is $175 per hour (qty 1 = 1 hour). Hardware buyers get up to one hour ($175) credited back on their order.
The Vertiv Liebert GXT5LI-10KGVRT3UXLN is a 10,000 VA / 10,000 W online double-conversion UPS built around a lithium-ion battery pack — the architecture that eliminates the VRLA maintenance cycle that forces data center and network closet crews to pull and replace batteries every three to five years. At 3U and hardwired input, this unit belongs in server rooms, edge compute deployments, and security operations centers where uptime is non-negotiable and battery lifecycle cost matters as much as the acquisition price. For organizations building out a power and UPS infrastructure, the GXT5LI-10KGVRT3UXLN sits at the high-capacity end of the Liebert GXT5 family.
The hardwired 200-240V input requires coordination with building electrical infrastructure — a licensed electrician must terminate the input feed. Output configuration flexibility (200-240VAC user-selectable) allows the unit to match the voltage standard of the protected equipment, making it practical for mixed-voltage rack environments common in international deployments or facilities with legacy equipment. The network and server equipment this UPS is designed to protect typically includes core switching, NVR appliances, access control servers, and edge compute nodes — all of which benefit from the zero-transfer-time double-conversion design.
For organizations evaluating UPS infrastructure for security operations, the GXT5 family integrates with Vertiv's Liebert monitoring ecosystem. Consult Vertiv's management card compatibility documentation for SNMP and remote monitoring options specific to this chassis. If you are building a complete uninterruptible power supply infrastructure and need to size runtime, runtime depends on battery module configuration — confirm with Vertiv's runtime calculator using your actual load profile, not the nameplate rating.
Q: Does the GXT5LI-10KGVRT3UXLN require a licensed electrician for installation?
A: Yes. The hardwired input (L1-L2/N-G) means there is no plug — a licensed electrician must terminate the branch circuit feed. At 10kW, branch circuit breaker sizing typically runs 40-50A at 240V. Factor electrician labor and conduit work into your project budget before ordering.
Q: What is the difference between this lithium-ion model and a standard VRLA GXT5?
A: The GXT5LI uses lithium-ion battery cells instead of valve-regulated lead-acid (VRLA) batteries. Li-ion chemistry delivers significantly longer battery service life and tolerates higher ambient temperatures better than VRLA, which typically requires replacement every 3-5 years. The tradeoff is a higher upfront cost that often pencils out favorably over a five-year total cost of ownership comparison.
Q: Will the GXT5LI-10KGVRT3UXLN fit in a standard 2-post open-frame rack?
A: Most 2-post open-frame racks are not appropriate for this unit. At 105 lbs and 35 inches deep, a 4-post enclosed cabinet with a proper UPS slide rail kit is the correct installation context. Confirm your cabinet's depth and weight rating before mounting.
Q: What certifications does the GXT5LI-10KGVRT3UXLN carry?
A: The unit is certified to UL 1778, FCC Part 15 Class A, IEC 62040-1:2008+A1 2013, IEC 62040-2 2nd Ed., IEC 62619 1st Ed. (lithium battery safety), IEC 61000-3-2, IEC 61000-3-12, and CISPR 22 Class A. IEC 62619 is particularly relevant for lithium-ion deployments subject to AHJ review.
Q: Is the output voltage fixed at 230VAC?
A: No. 230VAC is the default, but the output is user-configurable anywhere in the 200-240VAC range with ±1% regulation. This makes the unit usable in environments where the protected equipment requires a voltage other than 230V.
Q: Can this UPS operate in a warm server room or IDF closet above 40°C?
A: The rated operating range is 32°F to 104°F (0°C to 40°C). Above 40°C, the spec sheet documents a 10% output derating at 50°C — the unit will continue operating but at reduced capacity. For consistently warm spaces, either add cooling or derate your load sizing accordingly.

When I look at the GXT5LI-10KGVRT3UXLN, the spec that drives the deployment conversation is the unity power factor — 10,000 VA and 10,000 W are the same number, which means you are not giving up usable capacity to a 0.8 or 0.9 PF penalty the way you do with older UPS designs. For a fully populated 10kW load, that distinction is real money in avoided over-sizing.
Technical Highlights:
Deployment Considerations:
The GXT5LI-10KGVRT3UXLN is the right specification for a purpose-built security operations center or a high-density network closet where the project timeline is long enough that battery replacement cost is a real budget line — lithium-ion's extended service life changes the five-year TCO math in a way that justifies the premium over a VRLA equivalent at this power class.