Questions about this product? Free pre-sales support from a senior specialist — product questions, compatibility checks, BOM quotes, price confirmation — typically answered within one business day. Need camera placement or system design work? Engineering time is $175 per hour (qty 1 = 1 hour). Hardware buyers get up to one hour ($175) credited back on their order.
The APC by Schneider Electric SYPM10KF2 is a 10kW, 208V three-phase power module designed for the APC Symmetra PX UPS platform — specifically the PX 20, PX 40, and PX 100 frames. It serves two roles: drop-in replacement for a failed module in an existing chassis, or a capacity expansion unit when your facility's power demand has grown beyond the original build. Either way, the module slots into the existing frame without reconfiguring the entire UPS infrastructure. Lead time is typically two weeks, so order ahead of a planned maintenance window rather than waiting for a failure event.
The SYPM10KF2 uses a double-conversion online topology, meaning incoming AC is rectified to DC and then re-inverted to clean AC output — your critical loads never see raw utility power at all. At full 10,000W output, total harmonic distortion stays below 5%, which matters when you're powering sensitive networking or storage gear that reacts poorly to waveform noise. The output is a true sine wave, not a simulated or stepped approximation.
The SYPM10KF2 is engineered for the Symmetra PX modular UPS platform — confirmed compatible frames include the Symmetra PX 20kW, PX 40kW, and PX 100kW. The module occupies one power module bay in the frame. Capacity scaling is additive: each additional SYPM10KF2 module contributes 10kW to the frame's total available output, up to the frame's maximum. This architecture lets you right-size power capacity at installation and expand incrementally as load grows, rather than replacing the entire UPS when power demand increases.
The operating altitude ceiling is 3,333 feet (approximately 1,016m) at rated capacity. Deployments above this elevation may require derating — confirm with APC engineering if your site is at altitude. Operating humidity range is 0–95% non-condensing; storage humidity matches. Storage temperature range is 5°F to 104°F (-15°C to 40°C), so the module can be warehoused in an unheated space but should not freeze.
For rack and enclosure planning, the packaged dimensions are 31.3 in (W) × 23.4 in (L) × 8.9 in (H) at 61.84 lb shipped weight. Installed weight is 55.23 lb — plan for two-person installation. The single-cable connection keeps installation straightforward; the included installation guide covers the procedure.
Q: Which Symmetra PX UPS frames is the SYPM10KF2 compatible with?
A: The SYPM10KF2 is designed for the Symmetra PX 20kW, PX 40kW, and PX 100kW UPS frames. It functions as either a replacement module or a capacity expansion module within those frames.
Q: What is the output power rating of the SYPM10KF2?
A: The SYPM10KF2 delivers 10,000W (10kW) / 10,000VA at 208V three-phase output. Because the power factor is unity, the kW and kVA ratings are equal — there is no derating for power factor on the load side.
Q: What UPS topology does the SYPM10KF2 use?
A: Double-conversion online. Incoming utility AC is continuously rectified to DC, then inverted back to clean sine-wave AC output. There is no transfer time to battery — connected loads never experience a switching event during utility disturbances.
Q: What are the input power quality specs for the SYPM10KF2?
A: The module draws power at a 0.99 input power factor at full load and injects less than 5% total harmonic distortion back onto the input feed. Input frequency tolerance is 60 Hz ±3 Hz.
Q: Is the SYPM10KF2 suitable for outdoor or high-altitude installations?
A: No. The module is rated for indoor use only. Maximum operating altitude is 3,333 feet at full rated capacity. Installations above this elevation may require capacity derating. Storage altitude maximum is 15,000 feet.
Q: What are the safety and emissions certifications for the SYPM10KF2?
A: The SYPM10KF2 is cUL Listed and UL Listed, and complies with FCC Part 15 Class A (commercial environments), UL 60950, ISO 9001, and ISO 14001 standards.

The SYPM10KF2 is the module I recommend when a client needs to either recover a degraded Symmetra PX frame after a module failure or step up capacity incrementally — and the 10kW-per-slot architecture makes it genuinely useful for both scenarios. The 0.99 input power factor at full load is the spec I point to first: in a frame running four or five of these modules, the difference between 0.99 and a typical 0.9 PF draws several hundred fewer reactive volt-amps from the facility's distribution — that adds up on demand-metered utility accounts.
Technical Highlights:
Deployment Considerations:
This module is the right call for a brownfield Symmetra PX frame in a 208V three-phase data center or network operations center where the chassis is already installed and you're adding load capacity in 10kW increments rather than forklift-upgrading the entire UPS platform.
Manufacturer-verified compatible cameras, recorders, mounts, accessories, and licenses for this product. Adjust quantities and add the entire bundle to your cart in one click.
Looking for more APC by Schneider Electric products? Shop the full APC by Schneider Electric catalog →
Support services and planning resources for commercial surveillance, access control, and infrastructure deployments.
Fixed scope • Fixed price