Questions about this product? Free pre-sales support from a senior specialist — product questions, compatibility checks, BOM quotes, price confirmation — typically answered within one business day. Need camera placement or system design work? Engineering time is $175 per hour (qty 1 = 1 hour). Hardware buyers get up to one hour ($175) credited back on their order.
Server Technology C2SG36TE-YCMFAM66 8.6kW Switched Rack PDU
Overview
The Server Technology C2SG36TE-YCMFAM66 is a PRO2-series Smart POPS rack PDU built for data center cabinets that need granular power visibility down to the individual outlet. Rated at 8.6kW on a 208V, 30A NEMA L21-30P input, this unit is designed for mid-to-high-density server and network racks where operators need to know exactly what each device is drawing, not just what the whole cabinet is pulling. C2SG36TE-YCMFAM66 combines 36 usable outlets across three connector types with per-outlet and per-inlet power sensing, giving facilities and network operations teams the granularity to catch a failing PSU or an overloaded branch before it trips a breaker.
Key Features
- Per-Outlet Power Sensing (POPS): Monitors current, voltage, watts, apparent power, crest factor, power factor, and energy at every individual outlet — useful when you need to bill back power by rack tenant or isolate which specific server is drawing abnormally.
- Per-Inlet Power Sensing (PIPS): Tracks the same metrics at the inlet level, so you can validate total load against the 8.6kW capacity and 24A rated current without walking the row with a clamp meter.
- 24x C13 + 12x Cx outlets: The Cx outlets are a UL-tested hybrid that accepts both C14 and C20 plugs, so a single PDU handles standard servers and higher-draw switches or storage arrays without ordering a separate outlet configuration.
- 3x NEMA 5-20R outlets: Covers standard North American equipment (monitors, KVMs, laptops) that doesn't use IEC power cords, without needing an adapter hanging off the rack.
- Branch Circuit Monitoring at 20A per breaker: Each branch is monitored individually with SNMP-based alerts before a circuit trips — catches an overloaded branch during a gradual rack build-out rather than after a 3am outage.
- UL 489 magnetic-hydraulic breakers, 10 kAIC interrupt rating: Meets the UL/IEC 62368-1 branch circuit protection requirement, which matters when the PDU is feeding a rack with a mix of legacy and modern gear on a shared circuit.
- Hot-Swap Network Card with Star Multi-Linking: Links up to four power circuits under one IP address, and the Expansion unit keeps network access alive if the Primary unit loses power — you don't lose remote visibility into the rest of the row because one circuit tripped.
- Auto-Flip Current Display: LED readout cycles per-phase current automatically, so three-phase load balancing during install doesn't require pulling up the web interface on a laptop cart.
- Temperature/Humidity Monitoring: Supports two external 10-ft probes per unit with SNMP alerting — relevant for cold-aisle/hot-aisle verification in colo or edge cabinets without a separate environmental sensor.
- Alternating-Phase Outlet Layout: Outlets are arranged to distribute load evenly across phases, reducing the chance of one leg running hot while another sits underutilized.
- 10/100/1000 Mbps Ethernet: Gigabit-capable management port for HTTP(S), SSH, Telnet, SNMP, (S)FTP, SMTP, Syslog, and LDAP(S) — fits into existing out-of-band management networks without a throughput bottleneck.
- 0°C to 60°C operating range: Wide enough for edge cabinets and non-climate-controlled telecom spaces, not just a conditioned data hall.
Integration & Compatibility
C2SG36TE-YCMFAM66 fits into standard remote power management workflows via SNMP, making it straightforward to pull into existing DCIM or monitoring dashboards alongside other rack-mounted infrastructure. At 70 inches long and 2.2 x 2.5 inches in cross-section, it's built as a vertical 0U mount for full-height rack cabinets — plan your rack accessories and cable management around a zero-U vertical strip rather than a horizontal rack-unit slot. For teams standardizing on Server Technology's PDU lineup across multiple rows, the Star Multi-Linking feature reduces the number of IP addresses and switch ports needed per line of racks — worth mapping out during network and PoE planning for the row. If you're speccing power alongside surveillance or compute racks, cross-reference this PDU's 8.6kW capacity against total nameplate draw before finalizing your NVR or server rack layout.
Frequently Asked Questions
Q: What input plug does the C2SG36TE-YCMFAM66 use?
A: It terminates in a NEMA L21-30P plug rated for 208V at 30A input (24A rated current), so confirm your PDU whip or receptacle matches before ordering.
Q: How many outlets does the C2SG36TE-YCMFAM66 have?
A: 36 total: 24x C13, 12x Cx (accepts both C14 and C20 plugs), and 3x NEMA 5-20R.
Q: Does the C2SG36TE-YCMFAM66 monitor power at the outlet level?
A: Yes — it includes Per-Outlet Power Sensing (POPS) and Per-Inlet Power Sensing (PIPS), tracking current, voltage, watts, apparent power, crest factor, power factor, and energy.
Q: What is the operating temperature range for the C2SG36TE-YCMFAM66?
A: 0°C to 60°C operating, with -40°C to 85°C storage range, both at 8%RH to 90%RH humidity.
Q: What network protocols does the C2SG36TE-YCMFAM66 support?
A: HTTP(S), SSH, Telnet, SNMP, (S)FTP, SMTP, Syslog, LDAP(S), and RS-232 serial over a 10/100/1000 Mbps Ethernet port.
Q: What certifications does the C2SG36TE-YCMFAM66 carry?
A: UL 62368-1, CSA C22.2 No. 62368-1, FCC Part 15 Class A, and CAN ICES-003 Class A.

The spec that jumps out on the C2SG36TE-YCMFAM66 (often searched as C2SG36TE YCMFAM66) is the outlet mix — 24x C13, 12x Cx, and 3x NEMA 5-20R on one 8.6kW unit. I've specced a lot of PDUs where the Cx-style hybrid outlet wasn't available yet, meaning you'd guess wrong on C14 vs C20 density and end up short a few ports. Here you get both plug types on the same 12 outlets, which takes that guesswork out of the BOM.
Technical Highlights:
- 8.6kW at 208V / 30A (24A rated): Gives real headroom for a rack running mixed 1U servers and a couple of higher-draw switches without derating concerns on the branch breakers.
- Per-Outlet and Per-Inlet Power Sensing: POPS and PIPS together mean you can validate total draw against the 24A rated current at the inlet, then drill into which specific outlet is the outlier — no separate power meter needed during a capacity audit.
- 20A branch breakers with 10 kAIC interrupt rating: UL 489 magnetic-hydraulic breakers on each branch, which is the detail an electrical inspector will actually check on a data hall walkthrough.
Deployment Considerations:
- At 70 inches long, this is a full 0U vertical mount — measure your rack's rear channel clearance before ordering, especially in narrower colo cabinets.
- The Star Multi-Linking feature only pays off if you're deploying multiple linked circuits under one IP — for a single standalone rack it's a nice-to-have, not a driver.
This is the right call for a colocation or enterprise data hall row where you're standardizing rack power monitoring across dozens of cabinets and need per-outlet billing data, not just an aggregate amp reading at the panel.
Compare with similar
Server Technology Smart Pops Master PRO2 - C2SG36TE-YCMFAM66
Build Your Complete System
Manufacturer-verified compatible cameras, recorders, mounts, accessories, and licenses for this product. Adjust quantities and add the entire bundle to your cart in one click.
Looking for more Server Technology products? Shop the full Server Technology catalog →
System Design, Deployment & Technical Support
Support services and planning resources for commercial surveillance, access control, and infrastructure deployments.
Fixed scope • Fixed price
System Design Assistance
- Get help validating product compatibility
- Coverage requirements
- Storage planning and deployment architecture before you buy.