Questions about this product? Free pre-sales support from a senior specialist — product questions, compatibility checks, BOM quotes, price confirmation — typically answered within one business day. Need camera placement or system design work? Engineering time is $175 per hour (qty 1 = 1 hour). Hardware buyers get up to one hour ($175) credited back on their order.
Server Technology C2S36CE-DFME2M66 Switched Rack PDU
Overview
The Server Technology C2S36CE-DFME2M66 is a 36-outlet vertical rack PDU built for data center and server room deployments where per-outlet visibility and remote control matter more than a basic power strip. Rated for 208V input at 40A through a CS8365 3P+G 50A plug, it delivers 14.4kW of usable input capacity — enough headroom for a fully populated rack of switching, storage, or compute without tripping a branch breaker mid-shift. At 70 inches tall and only 2.2 inches wide by 2.5 inches deep, the C2S36CE-DFME2M66 mounts in the vertical 0U rail space most cabinet vendors leave open, so it doesn't eat into usable U-space you'd rather fill with servers.
Key Features
- 36 Outlets (C13/C19 mix): C13 outlets are rated up to 12A and C19 up to 16A at 208V L-L, giving you enough outlet diversity to feed both standard servers and higher-draw switches or blade chassis from one unit without a second PDU.
- Branch Circuit Breakers at ≤16A: Each branch is individually protected, so a fault or overload on one outlet group trips locally instead of taking down the whole rack — a real factor when you're running mixed workloads on shared power.
- 10 kAIC Interrupt Rating: Rated to safely clear higher fault currents without catastrophic failure of the PDU itself, which matters in facilities with higher available fault current on the upstream panel.
- Per-Outlet and Input Metering (±1% accuracy): Current, voltage, active power, apparent power, and power factor are all measured at ±1% accuracy (±3% for power factor and branch current), so capacity planning and billing/chargeback numbers are trustworthy instead of ballpark.
- 10/100/1000 Mbps Ethernet + RS-232: Gigabit management over copper plus a serial RJ-45 console port means you can manage the PDU in-band or out-of-band, useful when the network segment it lives on is down and you still need console access.
- Broad Protocol Support: HTTP/HTTPS, SSHv2, SNMPv2c/v3, LDAPv3/LDAPS, TACACS+, and RADIUS are all supported, so the PDU can slot into an existing centralized auth and monitoring stack instead of running as an island with its own local accounts.
- Quiescent Draw Under 10W: The PDU itself consumes less than 10W unloaded, so the overhead it adds to your rack power budget is close to negligible.
- Two Temperature/Humidity Sensor Inputs (4P4C): Lets you monitor rack-level environmental conditions from the same management interface as power, instead of running a separate environmental monitoring appliance.
- Operating Range 0°C to 60°C: Rated well past typical data center setpoints, giving margin for hot-aisle containment designs or facilities running warmer ASHRAE envelopes to save on cooling costs.
- Link Port (RJ-12): Supports linking multiple PDU units together for centralized management across a cabinet row, cutting down on the number of individual IP addresses and management sessions you have to track.
Integration & Compatibility
The C2S36CE-DFME2M66 (often searched as C2S36CE DFME2M66) supports IPv4/IPv6 and FTP/SFTP for firmware and config management, which matters if your data center standard requires IPv6-only management VLANs or secure file transfer for firmware pushes. UL 62368-1 and CSA C22.2 No. 62368-1 listing cover US and Canadian electrical safety compliance, while FCC Part 15 Class A and CAN ICES-003 Class A cover EMI requirements for commercial and industrial environments — relevant if the PDU shares a room with sensitive RF or networking gear. For broader rack power planning, a rack PDU like this one pairs naturally with a review of your PoE and power budget planning before you commit to a cabinet layout, and with NVR or switch gear from the same rack if you're building out a server room alongside a security deployment. Browse the full Server Technology lineup for lower-outlet-count or single-phase variants if this 36-outlet 208V model exceeds what your cabinet needs.
Frequently Asked Questions
Q: What input voltage and plug does the C2S36CE-DFME2M66 require?
A: It runs on 208V, 40A rated input through a CS8365 3P+G 50A plug, delivering up to 14.4kW of input capacity.
Q: How many outlets does the C2S36CE-DFME2M66 have?
A: 36 total outlets, a mix of C13 (rated up to 12A at 208V L-L) and C19 (rated up to 16A at 208V L-L).
Q: Can I monitor power usage per outlet on the C2S36CE-DFME2M66?
A: Yes. It provides input and outlet-level metering for current, voltage, active power, apparent power, and power factor, with ±1% accuracy on current, voltage, active power, and apparent power measurements.
Q: What's the warranty on the C2S36CE-DFME2M66?
A: It carries a 2-year limited manufacturer warranty.
Q: What management protocols does the C2S36CE-DFME2M66 support?
A: HTTP/HTTPS, TLSv1.2, SSHv2, Telnet, SNMPv2c/v3, IPv4/IPv6, LDAPv3/LDAPS, TACACS+, RADIUS, and FTP/SFTP.
Q: What's the operating temperature range for the C2S36CE-DFME2M66?
A: 32°F to 140°F (0°C to 60°C) with 8%RH to 90%RH non-condensing humidity.

What stands out on the C2S36CE-DFME2M66 is the branch-level protection combined with ±1% metering accuracy — that combination is what separates a real monitored PDU from a switched strip with a display bolted on. This is a 208V, 40A input unit pulling up to 14.4kW through a CS8365 plug, so make sure your panel and receptacle match before you spec it.
Technical Highlights:
- 36 outlets, C13 (≤12A) / C19 (≤16A): Enough outlet diversity to run a mixed rack of 1U servers and higher-draw switch gear off one PDU instead of splitting the load across two units.
- 10 kAIC interrupt rating: Gives the unit margin to clear fault currents safely in facilities where upstream fault current is higher than a typical small server closet.
- Quiescent draw under 10W: The PDU's own overhead barely registers against a 14.4kW input budget, so your usable capacity planning numbers stay close to nominal.
Deployment Considerations:
- The CS8365 3P+G 50A plug is a specific locking connector — confirm your PDU whip or receptacle is already CS8365-terminated before ordering, since this isn't a standard NEMA drop.
- At 70 inches tall and 2.2 inches wide, this is a 0U vertical mount — it needs open vertical rail space in the cabinet, not horizontal U-slots, so check cabinet clearance before assuming it fits an existing enclosure.
This is the right call for a data center cabinet running mixed 1U/2U servers alongside a switch stack, where you need branch-level circuit protection and outlet-level power metering for capacity planning — not for a small IT closet where a basic unmonitored strip would do.
Compare with similar
Server Technology Smart Master PRO2 (36) - C2S36CE-DFME2M66
Build Your Complete System
Manufacturer-verified compatible cameras, recorders, mounts, accessories, and licenses for this product. Adjust quantities and add the entire bundle to your cart in one click.
Looking for more Server Technology products? Shop the full Server Technology catalog →
System Design, Deployment & Technical Support
Support services and planning resources for commercial surveillance, access control, and infrastructure deployments.
Fixed scope • Fixed price
System Design Assistance
- Get help validating product compatibility
- Coverage requirements
- Storage planning and deployment architecture before you buy.
Deployment & Configuration Support
- Access fixed-scope support for rollout planning
- User setup guidance
- Migration and system standardization across single-site or multi-site deployments
Guides, Tools & Calculators
- PoE requirements
- Storage retention
- Camera selection and deployment methodology