APC by Schneider Electric
SKU: AP7869B
Overview
Manufacturer-verified compatible cameras, recorders, mounts, accessories, and licenses for this product. Adjust quantities and add the entire bundle to your cart in one click.
Overview
Questions about this product? Free pre-sales support from a senior specialist — product questions, compatibility checks, BOM quotes, price confirmation — typically answered within one business day. Need camera placement or system design work? Engineering time is $175 per hour (qty 1 = 1 hour). Hardware buyers get up to one hour ($175) credited back on their order.
The AP7899B is a zero-U, vertically mounted, three-phase metered rack PDU designed for high-density data center and server room deployments where 208V three-phase power delivery and real-time load monitoring are non-negotiable. Rated at 14.4kW (14,400 VA) with a 50A CS8365 input plug and a 10-foot (3.05m) power cord, the AP7899B fits into the rear vertical channel of a standard equipment rack without consuming a single rack unit — freeing every U for revenue-generating infrastructure.
This unit belongs to APC's APC by Schneider Electric rack power distribution line, purpose-built for environments that demand granular load visibility without the added cost of switched or outlet-level control. If you're managing colocation cages, dense compute rows, or high-draw storage arrays, this is the class of PDU to evaluate first.
The AP7899B is compatible with standard two-post and four-post open-frame racks as well as enclosed cabinets that include rear vertical mounting channels. Verify that your rack's rear channel supports a zero-U vertical PDU mount and that the mounting brackets (if required for your specific cabinet model) are on hand before installation.
As a metered PDU, the AP7899B provides local load readings but does not offer network connectivity, outlet switching, or remote monitoring without an add-on network management card — if those capabilities are required, evaluate a switched or networked PDU variant in the same family. For environments already running a network management layer, the metered form is typically sufficient as a supplement to existing DCIM or BMS infrastructure.
The outlet mix supports virtually all IEC-standard server and networking hardware. High-density compute deployments drawing 20A or more per device should plan their C19 allocation carefully — four C19 outlets at the rated draw limits of connected equipment can approach the per-phase current ceiling quickly. Pair with a compatible UPS sized for the full 14.4kW load for protected runtime.
Q: What input plug does the AP7899B use, and what panel receptacle does it require?
A: The AP7899B uses a CS8365 locking plug rated for 50A at 208V three-phase. Your panel or power whip must have a matching CS8365R or equivalent locking receptacle. Confirm with your facilities team before ordering.
Q: How many outlets does the AP7899B have, and what types?
A: The AP7899B has 30 total AC outlets: 24×C13, 4×C19, and 2×NEMA L6-30R. C13 serves standard servers and networking gear; C19 serves high-draw equipment; L6-30R provides locking 208V connections for high-current appliances or sub-distribution.
Q: What is the maximum load capacity of the AP7899B?
A: The AP7899B is rated at 14,400 VA (14.4kW) at 208V. Maximum total input current is 50A, with a maximum of 40A per phase on the three-phase circuit. Plan your connected load to stay within the 40A-per-phase limit to avoid overload events.
Q: Does the AP7899B provide remote monitoring or outlet switching?
A: No. The AP7899B is a metered PDU — it provides local current monitoring at the inlet level but does not include network connectivity, remote monitoring, or outlet-level switching. If those capabilities are required, a switched or network-enabled PDU variant should be evaluated instead.
Q: What rack mounting style does the AP7899B use?
A: The AP7899B is a zero-U (0U) PDU designed for vertical mounting in the rear channel of a standard equipment rack. It does not occupy horizontal rack units, preserving full rack density for active equipment.
Q: Is the AP7899B RoHS compliant?
A: Yes. The AP7899B carries both RoHS and REACH compliance certifications, confirming restricted substances compliance for EU and international procurement requirements.

The AP7899B is one of those PDUs that earns its place in a high-density row by doing exactly what it says: distributing 14.4kW of three-phase 208V power across 30 outlets in a zero-U footprint, with enough outlet variety to handle a mixed server population without adapter sprawl. The 40A-per-phase maximum is the number to keep in front of you during capacity planning — it's the real ceiling, not the 50A total input figure.
Technical Highlights:
Deployment Considerations:
This PDU is the right fit for a colocation or enterprise data center row where cabinet density is at a premium, three-phase 208V power is available at the rack, and the monitoring requirement is satisfied by local metering plus an existing DCIM overlay — not for edge deployments or remote sites where you need remote outlet control or network-based alerting at the PDU level.