Questions about this product? Free pre-sales support from a senior specialist — product questions, compatibility checks, BOM quotes, price confirmation — typically answered within one business day. Need camera placement or system design work? Engineering time is $175 per hour (qty 1 = 1 hour). Hardware buyers get up to one hour ($175) credited back on their order.
The AP8861US is a zero-U, 3-phase metered rack power distribution unit rated at 5,700 VA / 5.7kW on a 208V input — purpose-built for high-density server and network equipment cabinets where per-unit outlet count, branch-level current visibility, and space efficiency all matter. With a NEMA L21-20P input plug, 36 IEC C13 outlets, 6 IEC C19 outlets, and 2 NEMA 5-20R convenience outlets, it covers the full range of rack-resident loads from 1U servers to high-draw UPS or KVM equipment without requiring a secondary PDU. Explore the full APC by Schneider Electric power distribution catalog for additional form factors and capacities.
Zero-U mounting means the AP8861US installs vertically along the interior rail channel of a standard 600mm or 800mm deep cabinet — it consumes zero rack units of usable space, leaving every U position available for revenue-generating gear. That distinction matters in colocation cages, edge deployments, and enterprise wiring closets where every rack unit carries real cost. The 3-phase, 20A input at 208V delivers 5.7kW of available load capacity — substantially more than a single-phase 20A/120V circuit, and sufficient to power a fully loaded 42U compute or network switch cabinet without an intermediate PDU distribution panel.
The AP8861US fits any cabinet with a vertical zero-U mounting rail channel — APC NetShelter SX, SV, and VX series are native fits, and most third-party rack enclosures of 600mm or greater depth support vertical PDU mounting. The NEMA L21-20P input requires a 3-phase 20A/208V circuit — confirm your facility's panel configuration before ordering. In single-phase or 120V environments, this unit is not the correct choice; APC's AP78xx series covers single-phase 120V applications.
On the load side, IEC C13 and C19 power cords are the global standard for rack-mount IT equipment — no proprietary connectors, no adapter chains. The 2 NEMA 5-20R outlets accept any North American 5-20P plug, covering management gear that hasn't migrated to IEC terminations. This PDU does not include network management connectivity (no RJ-45 management port); it is a locally metered unit. If remote power monitoring via SNMP, web browser, or REST API is required, the APC Rack PDU AP88xx series with network management cards addresses that use case.
Q: What input plug does the AP8861US require, and what circuit should I provision?
A: The AP8861US uses a NEMA L21-20P 3-phase locking plug and requires a 20A, 208V 3-phase circuit. Confirm your facility panel supports a 3-phase 208V feed before deployment — this unit is not compatible with single-phase 120V or 240V circuits.
Q: How many outlets does the AP8861US provide, and what types?
A: 42 total: 36 IEC 60320 C13 (standard server/switch loads), 6 IEC 60320 C19 (high-draw equipment up to 16A+), and 2 NEMA 5-20R (North American plug compatibility for management or console devices).
Q: Does the AP8861US support remote power monitoring or outlet switching?
A: No. The AP8861US is a metered PDU — it provides local current monitoring at the unit level, not remote SNMP or web-based monitoring. There is no network management port. For remote power monitoring or outlet-level switching, the APC Switched or Metered-by-Outlet PDU families are the appropriate alternatives.
Q: Does the AP8861US occupy rack unit space?
A: No. It is a Zero-U PDU, meaning it mounts vertically in the cable management channel of the rack and does not consume any rack unit (U) positions. All 42U (or however many your cabinet has) remain available for equipment.
Q: What is the total power capacity of the AP8861US?
A: The nominal input power is 5,700 VA (5.7kW) at 208V, 3-phase, 20A input. Actual usable load should be derated to 80% of rated capacity (4,560W) per NEC continuous load guidelines for the circuit feeding the PDU.
Q: What is the difference between the AP8861US and APC Switched PDUs?
A: The AP8861US is a metered PDU — it monitors input current locally but does not allow remote control of individual outlets. APC Switched PDUs add per-outlet or per-group remote switching and monitoring via a network management card, enabling remote power cycling. Choose metered when visibility is sufficient; choose switched when remote reboot capability is required.

The AP8861US is the unit I reach for when a rack build calls for 3-phase 208V distribution and the customer doesn't need outlet-level switching — the 5,700 VA capacity and 42-outlet count handle a fully populated cabinet without a secondary PDU, and zero-U placement means you're not trading equipment space for power hardware.
Technical Highlights:
Deployment Considerations:
Best fit: high-density 208V 3-phase cabinets in enterprise data centers, colocation deployments, or security operations centers running NVR servers and network infrastructure where load monitoring is required but outlet-level switching is not.