Questions about this product? Free pre-sales support from a senior specialist — product questions, compatibility checks, BOM quotes, price confirmation — typically answered within one business day. Need camera placement or system design work? Engineering time is $175 per hour (qty 1 = 1 hour). Hardware buyers get up to one hour ($175) credited back on their order.
Server Technology C4G36RA-5CBD2FE1 415V Switched POPS Rack PDU
Overview
The Server Technology C4G36RA-5CBD2FE1 is a 415V, 17.3kW switched rack PDU built for data center and colocation racks that need outlet-level power visibility, not just a total load reading. It combines Per-Outlet Power Sensing (POPS) with Per-Inlet Power Sensing (PIPS) so you get current, voltage, power, apparent power, crest factor, power factor, and energy data at both the whole-unit and individual-outlet level. This is a vertical zero-U form factor at 70 inches tall, 2.2 inches wide, and 2.5 inches deep — designed to mount in the rear channel of a rack cabinet without eating into usable U-space for servers or switches. C4G36RA-5CBD2FE1 (often searched as C4G36RA 5CBD2FE1) is positioned for hyperscale, colocation, and high-density edge deployments where 415V three-phase distribution is already in place.
Key Features
- 17.3kW input power capacity at 415V: supports high-density rack loads — GPU clusters, blade chassis, dense compute — without needing a second PDU in the same cabinet.
- NEMA L22-30P input plug, 30A input current, 24A rated: a locking three-phase plug that won't back out under vibration, with the 24A continuous rating giving you the headroom NEC 80% derating requires for a 30A circuit.
- 36 total outlets — 12x C13 and 24x HDOT Cx: the Cx outlets are UL-tested hybrids that physically accept either a C14 or C20 plug, so you're not stuck reordering PDUs when a server ships with a C19/C20 power cord instead of the standard C13/C14.
- Outlet ratings up to 16A @ 208V L-N (20A peak) on Cx, 12A @ 208V L-N (15A peak) on C13: gives you real per-outlet headroom for mixed loads — small switches on C13, higher-draw servers or storage arrays on Cx — on the same strip.
- Six branch circuit breakers, UL489 2-pole 20A trip, 10 kAIC interrupt rating: a fault on one outlet group trips its own breaker instead of taking down the whole PDU, which matters when you've got dozens of servers hanging off a single unit.
- Per-Outlet Power Sensing (POPS): per-outlet current, voltage, power, VA, crest factor, power factor, and energy — the data you need to right-size circuits and catch a single misbehaving PSU before it trips a breaker.
- Per-Inlet Power Sensing (PIPS): the same measurement set at the inlet level, useful for capacity planning across the whole rack rather than outlet-by-outlet.
- Input and output measurement accuracy of ±0.2% for both voltage and current: tight enough for real capacity billing and power-budget planning in colocation environments, not just rough load estimates.
- Hot-swappable controller: the controller — housing compute, display, and connectivity — can be replaced without powering down the outlets it manages, so a controller fault doesn't force a rack outage.
- 45-degree angled infeed: improves cable routing and strain relief in tight rear-of-rack spaces, and the bend radius is rated for 60A cords if you're standardizing infeed cabling across a row.
- Multi-unit linking and cascading, up to 16 PDUs on one IP: cuts down on IP address consumption and management overhead when you're running a full row of racks off this PDU family.
- Environmental monitoring for up to 12 daisy-chained DX2 SmartSensors: lets you tie temperature/humidity alerting into the same management interface as your power data, with SNMP alerts and email notifications.
Integration & Compatibility
Network access runs over 10/100/1000 Mbps Ethernet or 802.11 a/b/g/n Wi-Fi, with management through HTTP(S), SSH, Telnet, SNMP, (S)FTP, SMTP, Syslog, LDAP(S), or RS-232 serial — enough protocol coverage to fit into most existing DCIM or monitoring stacks without a proprietary agent. A 5V/500mA USB output is available for auxiliary peripherals at the rack. The unit is rated for operation from 32°F to 140°F (0°C to 60°C) at 5%–90% RH non-condensing, with storage tolerance down to -40°F and up to 185°F — a wide enough band for most conditioned data center floors as well as less-controlled edge and telecom cabinets. Certifications include UL 62368-1, CSA C22.2 No. 62368-1, FCC Part 15 Subpart B Class A, and CAN ICES-003 Class A. For the rest of the rack, pair this PDU with rack-mount NVRs or compute drawing from the same 415V circuit, and review a PoE and power planning guide before finalizing circuit assignments across a multi-PDU row. Browse the full Server Technology PDU catalog for lower-capacity or single-phase variants if 415V three-phase isn't available at your site, and check the power distribution units category for outlet configurations better suited to lower-density racks. A companion rack accessory lineup covers cable management for the angled infeed if you're standardizing a full row.
Frequently Asked Questions
Q: What input voltage and plug does the C4G36RA-5CBD2FE1 use?
A: It's a 415V PDU with a NEMA L22-30P input plug, rated for 30A input current (24A continuous rated) and 17.3kW input capacity.
Q: How many outlets does the C4G36RA-5CBD2FE1 have and what type?
A: 36 total outlets — 12x C13 and 24x HDOT Cx (a hybrid outlet that accepts both C14 and C20 plugs).
Q: Does the C4G36RA-5CBD2FE1 provide per-outlet power monitoring?
A: Yes. It includes Per-Outlet Power Sensing (POPS) and Per-Inlet Power Sensing (PIPS), reporting current, voltage, power, apparent power, crest factor, power factor, and energy, with ±0.2% measurement accuracy on both voltage and current.
Q: Can the C4G36RA-5CBD2FE1 be managed remotely?
A: Yes. It supports 10/100/1000 Mbps Ethernet and 802.11 a/b/g/n Wi-Fi connectivity, with management via HTTP(S), SSH, Telnet, SNMP, (S)FTP, SMTP, Syslog, LDAP(S), and RS-232 serial.
Q: What are the operating temperature limits for the C4G36RA-5CBD2FE1?
A: 32°F to 140°F (0°C to 60°C) at 5%–90% RH non-condensing during operation; storage range extends to -40°F to 185°F.
Q: Can multiple C4G36RA-5CBD2FE1 units be linked together?
A: Yes. Up to 16 PDUs can be daisy-chained from a primary unit over USB or Ethernet and managed through a single IP address.

The number that jumps out on the C4G36RA-5CBD2FE1 is the 17.3kW capacity off a 415V, 30A NEMA L22-30P infeed — that's a real high-density rack PDU, not a repackaged single-phase strip. I spec this class of unit when a rack is pushing dense compute or GPU nodes and the site already has three-phase 415V distribution run to the row.
Technical Highlights:
- 36 outlets (12x C13, 24x HDOT Cx): the Cx outlets accept both C14 and C20 cords, so you're not locked into a single power cord spec across a mixed rack of switches, servers, and storage.
- POPS + PIPS metering at ±0.2% accuracy: that's tight enough to actually trust for capacity billing or power-budget audits, not just a rough load gauge.
- Six UL489 branch breakers at 20A trip, 10 kAIC: outlet groups are fused independently, so one overloaded server doesn't take the whole PDU offline.
Deployment Considerations:
- Confirm your site actually runs 415V three-phase to the rack before ordering — the NEMA L22-30P infeed won't adapt to a standard 208V single-phase drop.
- At 70 inches tall and only 2.2 inches wide, this mounts in the rear vertical channel of the rack — check your cabinet's rear channel clearance against the 2.5-inch depth before ordering, especially in narrower colocation cabinets.
This is the right call for a colocation or hyperscale rack running dense, mixed-cord-type equipment on 415V power where you need outlet-level accountability for every device drawing from the C4G36RA-5CBD2FE1 — not a fit for a standard 120V/208V single-phase server room.
Compare with similar
Server Technology FOR CC-E1-128 - C4G36RA-5CBD2FE1
Build Your Complete System
Manufacturer-verified compatible cameras, recorders, mounts, accessories, and licenses for this product. Adjust quantities and add the entire bundle to your cart in one click.
Looking for more Server Technology products? Shop the full Server Technology catalog →
System Design, Deployment & Technical Support
Support services and planning resources for commercial surveillance, access control, and infrastructure deployments.
Fixed scope • Fixed price
System Design Assistance
- Get help validating product compatibility
- Coverage requirements
- Storage planning and deployment architecture before you buy.
Deployment & Configuration Support
- Access fixed-scope support for rollout planning
- User setup guidance
- Migration and system standardization across single-site or multi-site deployments
Guides, Tools & Calculators
- PoE requirements
- Storage retention
- Camera selection and deployment methodology