Panduit CBL CLT Polymer 1 Hole Config PK10
Glass-filled nylon, single-hole cable cleat designed to retain cables in place during low-to-intermediate short-circuit fault events
Manufacturer-verified compatible cameras, recorders, mounts, accessories, and licenses for this product. Adjust quantities and add the entire bundle to your cart in one click.
Questions about this product? Free pre-sales support from a senior specialist — product questions, compatibility checks, BOM quotes, price confirmation — typically answered within one business day. Need camera placement or system design work? Engineering time is $175 per hour (qty 1 = 1 hour). Hardware buyers get up to one hour ($175) credited back on their order.
The Panduit CCPL1H1923-X is a glass-filled nylon cable cleat engineered for short-circuit protection in low-to-intermediate fault current environments. Tested to peak fault currents of 69.5kA and certified to IEC 61914:2015, it retains cables on cable tray rungs when a fault event generates the electromagnetic forces capable of displacing unrestrained conductors. If you're specifying cable management for switchgear rooms, MCC lineups, or industrial power distribution where fault containment is required but conditions stop short of the harshest arc-flash environments, the CCPL1H1923-X is sized and rated for that middle tier.
Each pack contains 10 cleats, and each cleat mounts directly to a cable tray rung via a single user-supplied M10 bolt — no specialty tooling, no proprietary hardware beyond what's on the shelf in any electrical room.
The CCPL1H1923-X is designed for direct mounting to standard cable tray rungs. The single-hole configuration accepts a user-supplied M10 bolt — confirm rung thickness and thread engagement length before specifying on non-standard tray profiles. The cleat accepts cable outside diameters from 19 to 23mm; consult Panduit's cable management sizing guides to match cable OD to the correct cleat size if your conductor falls outside this range (the broader family covers 10–57mm OD via multiple SKUs). Competing cross-reference part numbers for this size tier include 1BC1923, 1F-13, 382AA02, 385AA03, and 385AA04 — useful when migrating from another manufacturer's cleat spec on a retrofit project. Not rated for submersion or continuous outdoor UV exposure without additional enclosure; verify installation environment against the –40°C to +60°C operating window and indoor/sheltered use intent.
M10 mounting bolt is user-supplied and not included.
Q: What cable diameter range does the CCPL1H1923-X accommodate?
A: The CCPL1H1923-X is designed for single cables with an outside diameter of 19 to 23mm. Cables outside this range require a different cleat size from the same product family.
Q: What fault current level has the CCPL1H1923-X been tested to?
A: It has been independently tested to peak fault currents of 69.5kA, making it appropriate for low-to-intermediate fault severity installations. Higher fault current environments require a higher-rated cleat.
Q: Is the CCPL1H1923-X certified to IEC 61914:2015?
A: Yes. The CCPL1H1923-X meets IEC 61914:2015 as verified by third-party laboratory testing — not manufacturer self-declaration.
Q: What fastener is required to mount the CCPL1H1923-X?
A: A single M10 bolt, user-supplied. The cleat mounts directly to a cable tray rung via the single mounting hole.
Q: How many cleats come in a pack?
A: Each pack contains 10 cleats.
Q: What is the operating temperature range for the CCPL1H1923-X?
A: The cleat is rated for –40°C to +60°C (–40°F to +140°F), covering standard indoor industrial environments including MCC rooms and cable tunnels.

The CCPL1H1923-X sits in a specific and deliberate tier of the Panduit cable cleat program — independently tested to 69.5kA peak fault current, IEC 61914:2015 certified by a third-party lab, and built from glass-filled nylon for installations where fault forces are real but the environment stops short of the most aggressive industrial conditions. If you're pulling a power distribution design together for an MCC room or indoor switchgear lineup and your fault current study comes in under 69.5kA, this cleat closes the cable restraint requirement without overspecifying into a heavier metallic cleat product.
Technical Highlights:
Deployment Considerations:
This cleat is the right specification for indoor MCC rooms, cable tray risers in commercial electrical rooms, and switchgear installations where the fault current study confirms available fault current at or below 69.5kA peak and the cable OD lands squarely in the 19–23mm range. If either constraint doesn't hold, re-size within the Panduit family rather than forcing the application.