Questions about this product? Free pre-sales support from a senior specialist — product questions, compatibility checks, BOM quotes, price confirmation — typically answered within one business day. Need camera placement or system design work? Engineering time is $175 per hour (qty 1 = 1 hour). Hardware buyers get up to one hour ($175) credited back on their order.
The Vertiv I10087 is a vertical metered rack power distribution unit built for high-density data center and IT closet environments where you need real-time power visibility without sacrificing the option to upgrade monitoring later. Carrying the full model number MN01D4B1-24D203-3TL21A0A10-S, this unit delivers 30A of 3-phase WYE input across 24 NEMA 5-20R receptacles at up to 8.6kW — giving you the outlet density and load capacity to service a fully populated rack without a second PDU. What sets the PowerIT line apart is the hot-swap upgradeable architecture: you can add an Interchangeable Monitoring Device (IMD) in the field to convert from metered to fully monitored without replacing the unit.
Manufactured in the USA and TAA Compliant (as well as Buy American Act COTS Compliant), the I10087 is a straightforward fit for federal, defense, and government IT environments where domestic-origin requirements are non-negotiable. Every unit ships 100% factory-tested. For a broader look at Vertiv's rack power and infrastructure line, the PowerIT family covers a wide range of input configurations and outlet counts.
The I10087 connects directly to any 30A, 3-phase WYE branch circuit terminated with a NEMA L21-30P receptacle — a standard outlet in purpose-built data centers and larger IT rooms. The 24 NEMA 5-20R outlets accept any standard C13-to-5-20P or 5-15P-to-5-20P server power cable, as well as 5-20P-terminated PDU whips. If your existing infrastructure uses a different input — such as a 3-phase delta or a single-phase 30A feed — this unit is not a fit without a transformer. For environments running rack PDUs across a mix of outlet types, Vertiv's PowerIT line includes variants with IEC C13/C19 outlets for international or dual-voltage environments.
For planning your rack power budget, pairing the I10087 with a compatible UPS upstream protects against utility fluctuations and gives you runtime during outages. The L21-30P plug feeds from most major UPS vendors' 30A 3-phase output receptacles. Consult your UPS vendor's output panel configuration before ordering.
If you need guidance on calculating rack power density and outlet allocation, the rack power planning guide walks through load balancing across phases and breaker sizing for mixed-equipment racks. For environments also managing structured cabling, see the cable management category for vertical and horizontal organizers that pair with this PDU's vertical mount profile.
Q: Is the Vertiv I10087 TAA compliant?
A: Yes. The I10087 is manufactured in the USA, TAA Compliant, and Buy American Act COTS Compliant — qualifying for federal, defense, and government procurement where domestic-origin requirements apply.
Q: What is the warranty on the I10087?
A: Vertiv covers the I10087 with a 5-year limited warranty.
Q: Can the I10087 be upgraded from metered to monitored after installation?
A: Yes. The PowerIT Upgradeable hot-swap design allows you to add a compatible Interchangeable Monitoring Device (IMD) in the field to convert the unit to monitored capability without replacing the PDU or taking the rack offline.
Q: What plug type does the I10087 require at the power source?
A: The I10087 uses a NEMA L21-30P Twistlock plug on a 10ft / 3m, 10/5 wire gauge cord. Your upstream power source must provide a matching L21-30P receptacle on a 30A, 3-phase WYE branch circuit.
Q: How many outlets does the I10087 provide, and how are they protected?
A: The I10087 has 24 NEMA 5-20R duplex outlets, grouped 4 per breaker across 6 independent 20A single-pole magnetic breakers. A fault on one breaker affects only its 4 outlets — the remaining 20 outlets stay live.
Q: What is the monitoring accuracy of the I10087's power measurements?
A: Phase-level measurements (kWh, W, VA, PF, V, A) are ANSI C12.1 and IEC 62053-21 compliant at 1% accuracy. Circuit/breaker current measurements are independently tested and verified at 2% accuracy.

The I10087 is the unit I recommend when an architect wants to defer the monitored PDU cost but needs to leave the door open — the hot-swap IMD slot means you're not locked into a forklift upgrade when the environment grows. The 1% accuracy on phase monitoring (ANSI C12.1 / IEC 62053-21) is worth calling out specifically: most facilities teams don't realize that PDU monitoring accuracy varies widely, and at 8.6kW loads that 1% delta matters for capacity planning dashboards.
Technical Highlights:
Deployment Considerations:
For a colocation row build or enterprise data center refresh where procurement needs TAA compliance and facilities teams want the option to add network-level PDU monitoring in a future budget cycle, the I10087 is the right unit to spec — not a near-term workaround, but a deliberate architecture decision.