APC by Schneider Electric FLUID COOLER 47KW - ACFC75268
47kW fluid cooler designed for high-density IT rack deployments where traditional air cooling reaches its limits
Manufacturer-verified compatible cameras, recorders, mounts, accessories, and licenses for this product. Adjust quantities and add the entire bundle to your cart in one click.
Questions about this product? Free pre-sales support from a senior specialist — product questions, compatibility checks, BOM quotes, price confirmation — typically answered within one business day. Need camera placement or system design work? Engineering time is $175 per hour (qty 1 = 1 hour). Hardware buyers get up to one hour ($175) credited back on their order.
The APC by Schneider Electric ACFC75272 is a roof-mounted evaporative fluid cooler rated at 47 kW at 110°F–120°F inlet conditions — engineered for data centers and industrial facilities where rejecting heat at the mechanical or roof level is a cleaner architectural decision than floor-space cooling. At 201.4 kg (444 lbs) and 2,400 mm wide, this is a unit you plan around during construction or major retrofit, not an appliance you drop in after the fact. It runs on 460 V, 3-phase, 60 Hz power, which places it squarely in commercial and industrial electrical infrastructure rather than light commercial buildings wired for single-phase or lower-voltage three-phase.
Evaporative fluid coolers occupy a specific niche: they reject heat from a closed hydronic loop — typically chilled water or glycol — by passing that fluid through a heat exchanger while evaporating water on the exterior. The result is lower leaving-fluid temperatures than a dry cooler can achieve in the same ambient conditions, without the refrigerant circuit and compressor overhead of a mechanical chiller. For facilities operating cooling towers or fluid-cooled UPS/battery systems as part of an APC by Schneider Electric power infrastructure stack, the ACFC75272 slots directly into that loop architecture.
The ACFC75272 integrates into closed-loop hydronic cooling systems — chilled water plants, free-cooling loops, or fluid-cooled APC by Schneider Electric UPS and power systems that include fluid-cooled battery cabinets or rectifiers. It is not a standalone data center cooling solution; it is the heat-rejection component in a larger loop that includes pumps, controls, and typically a primary cooling device (chiller or direct free-cooling coil). Sequence-of-operations design — particularly how the unit integrates with building automation or the facility's DCIM platform — is a separate engineering exercise not covered by the unit itself.
For facilities evaluating data center power and cooling infrastructure in parallel, the ACFC75272 pairs with APC's InRow and room cooling products where those products use a fluid-side connection. Confirm hydronic compatibility (flow rates, pressure drop, glycol concentration limits) with APC application engineering before finalizing the design.
Q: What cooling capacity does the ACFC75272 deliver, and under what conditions?
A: The ACFC75272 is rated at 47 kW at entering fluid temperatures of 110°F to 120°F. Actual output will vary with ambient wet-bulb temperature and fluid flow rate — confirm derating curves with APC for your specific climate and loop conditions.
Q: What electrical supply does the ACFC75272 require?
A: The unit requires 460 V, 3-phase, 60 Hz power. This is a commercial/industrial voltage level. Verify your facility's electrical distribution can supply this tap before ordering.
Q: Does the ACFC75272 include an onboard water tank?
A: No. The ACFC75272 does not have a removable or integral water tank. It requires a permanent make-up water connection and drain at the installation point. Water treatment for the evaporative section is the facility's responsibility.
Q: What are the structural requirements for roof installation?
A: The unit weighs 201.4 kg (approximately 444 lbs) operating and ships at 227.3 kg. The footprint is 2,400 mm wide × 993 mm deep. The roof structure must support this static load plus dynamic loads from fan operation. Engage a structural engineer to verify the curb design and roof capacity before installation.
Q: Is the ACFC75272 suitable for indoor installation?
A: No. The ACFC75272 is specified as a roof-mounted evaporative unit. It is designed for outdoor installation on a rooftop curb, where it can reject heat to the atmosphere and receive make-up water from building supply lines.
Q: What is the packaged size of the ACFC75272 for freight and rigging planning?
A: The packaged dimensions are 2,540 mm wide × 1,143 mm deep × 1,270 mm tall, with a packaged weight of 227.3 kg. Use these figures for crane reach calculations, sling geometry, and freight carrier selection.

The ACFC75272 is a unit that earns its place in a specific scenario: you have a fluid-cooled load — chilled water loop, glycol circuit, or fluid-side UPS infrastructure — and you need to reject 47 kW of heat at the roof without a compressor-based refrigerant circuit in the loop. At 460 V three-phase and 201.4 kg, this is not a plug-and-play appliance; it is a planned infrastructure component that belongs in the MEP drawings from day one.
Technical Highlights:
Deployment Considerations:
The ACFC75272 is the right specification for a new data center build or major mechanical retrofit where the cooling architecture already includes a closed hydronic loop and the electrical infrastructure supports 460 V three-phase — specifically facilities in the 40–60 kW heat rejection range that want evaporative efficiency without the complexity of a full cooling tower with open sump and drift eliminators.